Manual

Spectrex Inc. - SharpEye
TM
Mini IR3 Flame Detector Manual – TM 787100, Rev. D April 2011
10
Other fuels
The detector will react to other types of fires as follows:
Pan Fire Size: 1ft
2
(0.1m
2
)
Maximum Wind Speed: 6.5 ft/sec (2 m/sec)
Maximum Response Time: 10 sec
Table 3: Response Sensitivity Ranges
Type Of Fuel % Of Max. Distance at
each Sensitivity Range
Gasoline 100%
N-Heptane 100%
Alcohol 95% 75%
JP4 75%
Kerosene 75%
Diesel Fuel 70%
Methane* 30%
Propane* 30%
* 0.5m plume fire
Table 4: Sensitivity to other fire sizes
Fuel Fire Size Detection
Sensitivity
Distance Maximum Detection Time
20/20MI-1
Jet Fuel 2 x 2 ft 40 132 ft (40m) 10 seconds
Jet Fuel 2 x 2 ft 20 65 ft (20m) 8 seconds