Manual
Spectrex Inc. - SharpEye
TM
UV/IR (F) Flame Detector Manual – TM756100 Rev A, July 2005
11
e. Electrical Outputs:
Table 4. Dry Contacts Relays Ratings
Relay
Name
Type Normal position Maximum Ratings
Alarm SPDT N.O. 5A at 30VDC or 250 VAC
Fault SPST N.C. 5A at 30VDC or 250 VAC
5.2 Mechanical Specifications
a. Enclosure:
Aluminum: Chromate coating with Epoxy enamel finish
or
Stainless Steel 316: Electrochemical passivation coating
b. Explosion Proof
Ex II 2G SIRA 00ATEX 1160, 1162
EExd IIB + H
2
T5 Temp. -40°F (-40°C) to 160°F (70°C)
T4 Temp: -40°F (-40°C) to 185°F (85°C)
per EN 50014 & EN 50018
ATEX
EExde IIB + H
2
T5 Temp. -40°F (-40°C) to 160°F (70°C)
per EN 50014, 50018 & 50019
(see Appendix C)
FM (designed
to meet)
Class I Div. 1 Groups B, C and D;
Class II Div. 1 Groups E, F and G.
c. Electrical Modules: Conformal coating.
d. Electrical connection:
Either: Two 3/4” - 14NPT conduits.
or: Two M25 x 1.5 cable entries
e. Dimensions:
Detector: 5.2 x 5.2 x4.7in (132 x 132 x 120 mm)
f. Weight:
Alum. enclosure 8.1 lb. (3.7kg)
St.St. enclosure 14.3 lb (6.5kg)