Other Fuels:
The Detector will react to other fuels in standard fire conditions at maximum
response time of 3 seconds.
The sensitivity range to other fuels varies according to the fuel type. Table 1
below provides the sensitivity to other fuels relative to (as a percentage of) the
sensitivity to a standard gasoline fire source.
Table 1. Response Sensitivity Ranges
Type of Fuel % of Max. Distance at Each
Sensitivity Range
Gasoline 100%
N-Heptane 100%
Alcohol 95% 25%
JP4 75%
Kerosene 75%
Diesel Fuel 50%
Table 2: Response to Pyrotechnic Material
Material Description Time to Detection
RS41 Incendiary composition 2-3 msec
M206 IR Flare composition 3-4 msec
M14 Propellant 12-41 msec