Owner's manual

SPECIFICATIONS
NOMINAL
MODEL CURRENT OPTIONS
LPU 50 M - Outdoor enclosure with
150 clear door (NEMA 4X)
200 P - Positive ground
Specifications and product availability subject to change without notice.
PART NUMBERING KEY
EXAMPLE: Model
Nominal Current
Options
LPU - 50 - M
PARAMETERS UNITS VALUE
Nominal Voltage (Volts) 12-48
Array Voc., Max. (Volts) 95
Array Current, Continuous / Channel (Amps) 50
Array Current, Max / Channel (60 seconds) (Amps) 65
Primary Stage
Single Impulse Discharge Current,
8/20 µ sec waveform, Max. (Amps) 20,000
Impulse Life - 1000A,
10/1000 µ sec waveform, Min. (Surges) 400
Typ. (Surges) 600
DC Breakdown Voltage
Line to Ground (Volts) 150-300
Impulse Breakdown Voltage
Line to Ground
@ 100 V / µ sec, Typ. (Volts) 500
Max. (Volts) 750
@ 10 KV / µ sec, Typ. (Volts) 750
Max. (Volts) 1000
DC Holdover @ 200mA, Min. (Volts) 150
Secondary Stage
Peak Surge Capacity
8/20 µ sec, Max. (Amps) 1500
Peak Voltage Clamping
@1mA, Min. (Volts) 85
Max. (Volts) 115
Response Time, Typ. (Nanosec.) 50