Installation
SPEAKMAN
®
PO Box 191 Wilmington, DE 19899 Phone: 800-537-2107 Fax: 800-977-2747
Visit us on the web at www.speakmancompany.com
9/10
92-2368
5. veR 6 fo 5 egaP
Step 4: Unit Flushing-
a. After the assembly is complete, turn the hot and cold
water supplies on and check for leaks.
b. Activate the faucet to flush both the hot and cold sides of
fixture. Check all connections for leaks.
c. Install the aerator into the faucet outlet.
d. At this time activate faucet and then activate the eyewash
by pulling the handle and assure proper spray formation
and no leaks.
ALTERNATE INSTALLATION FOR
DEDICATED TEPID WATER SUPPLY
The unit is designed so the eyewash has
a dedicated supply line. This allows the
eyewash to have a tepid water supply.
Attach the tepid water supply to the
center adapter as shown in the figure
and your cold water
supply to the cold valve
ANSI Z358.1-1998 requires that the
delivered flushing fluid temperature shall
be tepid. Also, in circumstances where
chemical reaction is accelerated by
flushing fluid temperature, a medical
advisor should be consulted for the
optimum temperature of each application.
OPERATION
Eyewash- The eyewash is activated by pulling the handle out. Once the eyewash is activated, the
eyewash caps will flip off and water will come out of the aerated spray heads. The eyewash will
continually discharge water until the handle is manually pushed back into the off position.
TESTING PROGRAM
ANSI Z358.1 requires that all emergency equipment shall be tested weekly to verify proper operation
and inspected annually to assure conformance with ANSI Z358.1 requirement.
MAINTENANCE (CARE and CLEANING)
The gleaming finish of your SPEAKMAN Eyesaver
®
faucet can be cleaned by using mild soap and
warm water. Rinse thoroughly and dry immediately with a soft, clean cloth for best results.
body.