Installation

SPEAKMAN
®
PO Box 191 Wilmington, DE 19899 Phone: 800-537-2107 Fax: 800-977-2747
Visit us on the web at www.speakmancompany.com
9/10
92-2368
5. veR 6 fo 2 egaP
IMPORTANT: The supply line for plumbed units shall provide an uninterruptible supply of flushing fluid at
a minimum of 30 psi . of flow pressure. If shut off valve are installed in the supply line of the eyewash for
maintenance purposes, provisions shall be made to prevent unauthorized shut off.
OPTIONS
FLOW DATA
BO – Vandal-Resistant 0.5 gpm Flow Control LF – Laminar Flow Outlet 2.2gpm
ST – Serrated Tip with Vacuum Breaker 8 – 8” Gooseneck Spread
TW- Tepid Water Supply NA – Non-aerated Eyewash Sprayheads
FP – Foot pedal activation of faucet
Flow Pressure- psi.
(BAR)
30
(2.07)
40
(2.76)
50
(3.45)
60
(4.14)
70
(4.83)
80
(5.52)
Flow Rate- gpm
(LPM)
2.43
(9.2)
2.75
(10.4)
2.8
(10.6)
3.01
(11.4)
3.22
(12.2)
3.5
(13.2)
Distance Eyewash ins.
Plumb, ’A’ - (cm.)
10-1/2
(26.7)
12-1/2
(31.7)
14 (35.6) 14-1/2
(36.8)
16 (40.6) 17-1/2
(44.4)
CA- Low Lead for CA AB1953 Compliance