Installation

SPEAKMAN
®
PO Box 191 Wilmington, DE 19899 Phone: 800-537-2107 Fax: 800-977-2747
Visit us on the web at www.speakmancompany.com
9/10
92-2368
5. veR 6 fo 1 egaP
SPEAKMAN SAFETY PRODUCTS
Installation, Maintenance & Operation Instructions
SEF-1000 EYESAVER
®
FAUCET
DESCRIPTION
The SEF-1000 Eyesaver
®
faucet model allows a customer to convert their existing Speakman
widespread faucet into a Speakman SEF-1800 Eyesaver
®
faucet. The SEF-1800 combines a gooseneck
faucet with an independently operated eyewash.
SPECIFICATIONS
OPERATION: Pull handle to operate the eyewash
SUPPLY: Eyewash connection- ½” NPT male
Faucet Gooseneck- Inlets through the adapter tee have 3/8” male connections (SEF-1000
comes standard with 3/8” compression hoses to connect to Speakman widespread valves.
WIDESPREAD VALVES: Not included
FINISH: Chrome plated brass
EYEWASH ACTIVATION: Pull handle with graphics
EYEWASH SPRAYS: Aerated sprays.
EYEWASH FLOW RATE: 2.4 GPM at 30 psi. flowing. See flow data chart for additional information.
COUNTER THICKNESS: Up to 2” thick
PRESSURE: 30 psi. minimum flow pressure, 125 psi. maximum static pressure
COMPATABILITY: -Connects to any Speakman widespread faucet with flexible hose connections.
-Connects to any competitor widespread faucet that can connect to 3/8”
compression fittings via flexible hose. (hardware not supplied)
APPROVALS: Meets ASME A112.18.1, ANSI Z358.1 and CSA B125.1
VACUUM BREAKER (ST option): Approved by ASSE, UPC and CSA. Meets the ANSI/ASSE 1035
standard for “Laboratory Faucet Vacuum Breakers”, CSA B64.8 and UPC.
SHIPPING WEIGHT: 10 LBS.
Notes: All dimensions are in inches
(millimeters) unless otherwise
specified and are subject to change.