Installation
SPEAKMAN
®
400 Anchor Mill Rd. New Castle, DE 19720 Phone: 800-537-2107 Fax: 800-977-2747
8/25/16 www.speakman.com 92-1542-13
SPEAKMAN
®
SE-927
Installation, Maintenance & Operation Instructions
EYESAVER
LABORATORY DRENCH HOSE
DESCRIPTION
Deck mounted or hand held laboratory drench hose supplied with twin aerated heads with flip-off dust
covers, and self-closing valve, with automatic stay-open feature activated by squeeze handle.
SPECIFICATIONS
SPRAY HEAD: (2) AERATED, YELLOW PLASTIC SPRAY OUTLET, AND DUST COVER.
VALVE: 3/8” NPT FEMALE BRASS, CHROME-PLATED. SELF-CLOSING WITH AUTOMATIC
STAY-OPEN FEATURE.
ACTIVATOR: BRASS, CHROME-PLATED SQUEEZE HANDLE.
HOSE: 6’ REINFORCED, 750 PSI BURST PRESSURE.
FLANGE: BRASS, CHROME-PLATED.
INLET: 3/8” NPTM, SWIVEL CONNECTION.
SHIPPING WEIGHT: 3.27 LBS.
EMERGENCY SIGN: 7-7/8” X 7-7/8” PLASTIC WALL SIGN.
INSTALLATION
This unit is completely assembled and tested before shipment. At desired location on countertop (that has
a maximum thickness of 2-1/4”) drill a 1-1/8 to 1-1/4” diameter hole. Mount unit in hole using supplied
hardware. Connect a water supply to the unit (use pipe sealant on connection) that is an uninterrupted
source of potable water. Failure to use potable water can result in emergency units producing impure
or contaminated water causing possible further injury.
OPERATION
This drench hose is activated by squeezing the valve handle. Because of the automatic stay-open feature,
the valve will open and remain on upon activation. An aerated flow of water will discharge from the twin
outlets, and will continue to flow until the handle is squeezed, the stay-open plunger is pulled outward,
and the handle is released.
TESTING PROGRAM
The American National Standards Institute (ANSI) states that all safety emergency equipment shall
be activated on a weekly basis to flush the line and verify proper operation. Speakman Company furnishes
a testing record tag (91-0635) with each unit. On this tag the date of inspection and the inspectors initials
should be noted.
MAINTENANCE
Should you need parts to repair this unit, please reference the parts list below for correct part numbers.
Before any maintenance is done be sure to shut the water supply off.