Installation
SPEAKMAN
®
400 Anchor Mill Rd. New Castle, DE 19720 Phone: 800-537-2107 Fax: 800-977-2747
01/05/18 speakman.com 92-2733-09
SPECIFICATIONS
OUTER SHELL: PVC with Acrylic Cap.
INTERNAL STANCHION: 1” NPT Schedule 40 Galvanized Pipe & Fittings.
PIPE INSULATION: Closed Cell Rubber Foam.
SHOWER VALVE: Shower: 1” NPT Chrome Plated Brass Full Flow Stay-Open
Ball Valve.
SHOWER HEAD: 8” Dia. Yellow Plastic.
FLOW CONTROL: Internal 20 GPM Regulator.
SHOWER ACTIVATOR: Shower: Powder Coated High Visibility Yellow, Aluminum
Triangle Pull Rod.
SUPPLY INLET:
SE-7000 & SE-7000-220V50C: 1" NPT Male Bottom Supply
SE-7001 & SE-7001-220V50C: 1" NPT Male Top Supply
FLOOR FLANGE: Galvanized Steel with (3) 1/2” Dia. Mounting Holes on 7-7/8” Diameter
Bolt Circle.
EYE/FACE WASH:
SPRAY HEADS: (2) Yellow Plastic Spray Head Outlets with Flow Control.
VALVE: ½” NPT 3-Way Brass Full Flow Stay-Open Ball Valve.
FREEZE PROTECTION VALVE: ¾” NPT Brass, Self-Opening & Closing (40°) Valve.
ELECTRICAL SPECIFICATIONS:
AREA CLASSIFICATION: Class 1 Division 2, Groups B, C, And D Nema 4x.
ELECTRICAL SUPPLY:
(SE-7000 & SE-7001): 120 VAC, 60 Cycle, Single Phase.
(SE-7000-220V50C & SE-7001-220V50C): 220 VAC, 50 Cycle, Single Phase.
See additional electrical details on page #4.
JUNCTION BOX INLET: ¾” NPT Female (4) Outlet Box.
HEATING CABLE: 5 Watt/Ft. Self-Regulating Heating Cable with Metal Sheathing.
THERMOSTAT: Preset, Hermetically Sealed Single-Pole Contact Switch with
60°-70° Temperature Range.
NOTE: REFERENCE BELOW FOR MINIMUM 30MA GROUND FAULT PROTECTION
AND MINIMUM 15 AMP BREAKER.
SHIPPING WEIGHT: 87 LBS.
EMERGENCY SIGN: 12” X 7-7/8” PLASTIC WALL SIGN.
INSTALLATION INSTRUCTIONS
SECURING UNITS
SE-7000 / SE-7001 is equipped with a cast floor flange. Suitable anchors must be used to ensure that
the unit is rigid and properly secured before being used.
NOTE: If desired or required, additional straps or braces can be used to secure any unit.
(BE SURE NOT TO DRILL OR SCREW ANYTHING INTO THE OUTER PLASTIC SHELL.)
PLUMBING CONNECTION
1. The installer has the responsibility to see that the unit is connected to a potable water supply,
with a temperature that would allow the user to shower for a minimum of 15 minutes without
discomfort or shock due to cold water temperature. (ANSI Z358.1 recommends that water
temperature be between 60°-90° F.)
2. Inlet connection is 1" pipe. Supply line should have a suitable pressure to deliver a minimum of 30
PSI Flowing Pressure, and maximum 80 PSI static Pressure.