Specification Sheet

SPEAKMAN
400 ANCHOR MILL ROAD
NEW CASTLE, DE 19720
800-537-2107
800-977-2747
WWW.SPEAKMAN.COM
JU LY 2017
Architect/Engineer Approval Space:
P:
F:
W:
R:
550
4-1/2"in
7-5/8"
1-1/4" MINIMUM HOLE SIZE
18-1/2"
(3 HOSES)
130°
2-5/8"
6-3/8"
5-1/8"
2" MAX. DECK HEIGHT
9"
2-1/4"
8"
12°
4-7/8"
5-1/2"
6" MIN FROM WALL
OR OBSTRUCTION
65°
COLD SUPPLY
COLD HOSE
HOT SUPPLY
HOT HOSE
EYEWASH HOSE
24” MIN - 36” MAX
COUNTERTOP HEIGHT
SIDE VIEW (LESS HOSES)
FRONT VIEW
8-7/8"
5-1/4"
6” LONG HOSE
NOTE: UNLESS OTHERWISE SPECIFIED, ALL INLETS ARE 3/8” COMPRESSION WITH
FEMALE THREADS. UNLESS OTHERWISE SPECIFIED, ALL DIMENSIONS ARE IN INCHES
AND ARE SUBJECT TO CHANGE WITHOUT NOTICE.
SEF-1850
4-1/2"in
7-5/8"
1-1/4" MINIMUM HOLE SIZE
18-1/2"
(3 HOSES)
130°
2-5/8"
6-3/8"
5-1/8"
2" MAX. DECK HEIGHT
9"
2-1/4"
8"
12°
4-7/8"
5-1/2"
6" MIN FROM WALL
OR OBSTRUCTION
65°
COLD SUPPLY
COLD HOSE
HOT SUPPLY
HOT HOSE
EYEWASH HOSE
24” MIN - 36” MAX
COUNTERTOP HEIGHT
SIDE VIEW (LESS HOSES)
FRONT VIEW
8-7/8"
5-1/4"
6” LONG HOSE
NOTE: UNLESS OTHERWISE SPECIFIED, ALL INLETS ARE 3/8” COMPRESSION WITH
FEMALE THREADS. UNLESS OTHERWISE SPECIFIED, ALL DIMENSIONS ARE IN INCHES
AND ARE SUBJECT TO CHANGE WITHOUT NOTICE.
SEF-1850
24” MIN - 36” MAX
COUNTERTOP HEIGHT
SE-1850-TW ROUGH-IN DIAGRAM
COLD HOSE
HOT SUPPLY
HOT HOSE
EYEWASH HOSE
6” LONG HOSE
COLD SUPPLY
6” LONG HOSE
NOTE: DRAWING IS NOT TO SCALE. BE SURE TO KEEP THE
SE-370 AS CLOSE TO THE CENTER OF THE FAUCET BODY AS
POSSIBLE.
18” MAX
20” LONG HOSES
DIMENSIONS:
NOTE: 1. All dimensions are in inches (millimeters) unless otherwise specied and are subject to change without notice.
SEF-1850 Spray Plume Length and Flow
Flowing Pressure
30 psi 40 psi 50 psi 60 psi 70 psi 80 psi
2.07 Bar 2.76 Bar 3.45 Bar 4.14 Bar 4.83 Bar 5.52 Bar
Flow Rate
2.14 gpm 2.25 gpm 2.49 gpm 2.7 gpm 2.95 gpm 3.09 gpm
8.1 L/min 8.5 L/min 9.4 L/min 10.2 L/min 11.2 L/min 11.7 L/min
Eyewash Distance
Plume ”A”
12” 13” 15” 18” 21” 24”
30.5 cm 33 cm 38.1 cm 45.7 cm 53.3 cm 61.0 cm
The faucet spout was designed to swivel from left to right. If a
non-swivel spout is preferred, remove top cover from body. Next,
remove allen head set screw from position “1” as seen below.
Center the spout between the handles and install the previously
removed set screw into position “2” and tighten (DO NOT
OVERTIGHTEN). Replace cap.
Lift eyewash handle to activate the eyewash and test for proper
operation. See chart and notes at right.
1
2
psi bar gpm L/min in. cm.
30 2.07 2.14 8.1 12 30.5
40 2.76 2.25 8.5 13 33.0
50 3.45 2.49 9.4 15 38.1
60 4.14 2.70 10.2 18 45.7
70 4.83 2.95 11.2 21 53.3
80 5.52 3.09 11.7 24 61.0
FLOWING
PRESSURE
FLOW RATE
PLUME
DISTANCE "A"
SEF-1850
psi bar gpm L/min in. cm.
30 2.07 2.15 8.1 17 43.2
40 2.76 2.24 8.5 18 45.7
50 3.45 2.47 9.3 20 50.8
60 4.14 2.71 10.3 23 58.4
70 4.83 2.95 11.2 27 68.6
80 5.52 3.13 11.8 29 73.7
SEF-1850-8
FLOWING
PRESSURE
FLOW RATE
PLUME
DISTANCE "A"
11
12
Eyewash Flow Data
A
NOTE: If plume heights are low, check to ensure that your supply valves are
fully open. If there is a noticeable height difference between the two plumes,
remove the aerators and flow controls and remove any debris that would
inhibit the flow of water.
NOTE: Before testing, you must remove tape from Eyewash Caps.