Installation Sheet

psi bar gpm L/min in. cm.
30 2.07 2.14 8.1 12 30.5
40 2.76 2.25 8.5 13 33.0
50 3.45 2.49 9.4 15 38.1
60 4.14 2.70 10.2 18 45.7
70 4.83 2.95 11.2 21 53.3
80 5.52 3.09 11.7 24 61.0
FLOWING
PRESSURE
FLOW RATE
PLUME
DISTANCE "A"
SEF-1801
psi bar gpm L/min in. cm.
30 2.07 2.15 8.1 17 43.2
40 2.76 2.24 8.5 18 45.7
50 3.45 2.47 9.3 20 50.8
60 4.14 2.71 10.3 23 58.4
70 4.83 2.95 11.2 27 68.6
80 5.52 3.13 11.8 29 73.7
SEF-1801-8
FLOWING
PRESSURE
FLOW RATE
PLUME
DISTANCE "A"
Eyewash Flow Data
A
NOTE: If plume heights are low, check to ensure that your supply valves are
fully open. If there is a noticeable height difference between the two plumes,
remove the aerators and flow controls and remove any debris that would
inhibit the flow of water.
23
Turn on HOT and COLD handles of faucet and allow water to run for
one minute to flush any debris from faucet. Turn off faucet and install
aerator with supplied aerator wrench.
The spout was designed to swivel from left to right. If a
non-swivel spout is preferred, remove top cover from body.
Remove allen head set screw from position (1) as seen below.
Center the spout between the handles and install the previously
removed set screw into position (2) and tighten (DO NOT
OVERTIGHTEN). Replace cap.
2
1
24