Installation Guide
SPEAKMAN COMPANY
SE-911 Installation, Maintenance & Operation Instructions
DESCRIPTION
Stay-Open ball valve for emergency showers.
SPECIFICATIONS
VALVE: 1” NPT Female Brass, Nickel-Plated. Stay-Open Ball Valve.
INLET: 1” NPT Female.
OUTLET: 1” NPT Female.
SHIPPING WEIGHT: 3 lb.
SE-911-CR
SE-911 With 8” and 3” S/S Rings on #3 S/S Chains.
SHIPPING WEIGHT: 3 lb.
SE-911-PR
SE-911 With Powder Coated Yellow, Aluminum Triangular Pull Rod.
SHIPPING WEIGHT: 6 lb.
SE-911-SS
SE-911 With Stainless Steel Ball Valve, and Stainless Steel Pull Rod.
OPTIONS
INSTALLATION
Assemble valve to a horizontal or vertical water supply that has an uninterrupted source of potable water. Use pipe sealant on
all joints. Failure to use potable water can result in emergency units producing impure or contaminated water causing possible
further injury.
OPERATION
This valve is activated one of two ways, depending on the model in question.
1. SE-911-PR: Valve is activated by pulling downward on the aluminum pull rod, and is deactivated by manually pushing
the pull rod back to the off position.
2. SE-911-CR: Valve is activated by pulling downward on the 8” dia. stainless steel ring, and is deactivated by pulling
downward on the 3” dia. stainless steel ring.
Both model valves will discharge water until they are manually shut off following the instructions above.
TESTING PROGRAM
The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated on a weekly
basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag
(91-0635) with each unit. On this tag the date of inspection and the inspectors initials should be noted.
◊ SSBV1
(1” Stainless Steel Valve)