Span 1-00800-xx Installation Manual (rev. 2022-01-28) 9
Install Conduit
● The Span Panel allows conduit entry through the top, bottom, lower sides, and rear section of the panel.
● For top conduit entry, install a SquareD A-series threaded hub.
● Before removing knockouts, plan conduit routes and corresponding knockout locations and sizes on the enclosure. Be sure to
allow adequate clearance for conduit routing and anchoring. Conduit installation must comply with applicable fill limits and
electrical codes.
Allowable Conduit Entry Locations (shown in blue)
CAUTION: Do not punch conduit holes in any location on the enclosure that would allow moisture to enter the unit.
CAUTION: Follow guidance in NEC Chapter 3 and any local AHJ requirements for cable type selection. Consider exterior
surface and flush mounted installations as wet/damp conditions and use conduit accordingly. When installed in wet/damp
locations cable routed through the bottom face must be wet- or damp-rated.
NOTE: Additional conduit holes can be punched in the top sections of the panel. Note the locations of antennas and wires
inside the panel before cutting. Be careful to keep metal shards from coming into contact with any energized parts. Use
appropriate fittings for the location.
NOTE: Use care when drilling and confirm that fittings are the correct size and NEMA rating for the installation location
before proceeding.
NOTE: When top conduit entry locations are not used for wire entry, it must be sealed properly with top hub closing plate.