Span 1-00800-xx Installation Manual (rev. 2022-01-28) 5
PREPARING TO INSTALL
1. Unpacking and Inspecting the Panel
Inspect the packaging and Span Panel for damage. Ensure you have received the following components:
● Span Panel (with main bonding jumper pre-installed) and door (packaged separately)
● Getting Started card (with instructions for homeowner to download Span Home App)
● Breaker label schedule sheet
● Accessories:
● (1) Conduit hub closing plates (SquareD ACPCP) (pre-installed)
● (2) SquareD service entrance barrier covers (pre-installed)
● SquareD 200 A main breaker (pre-installed)
● Spare fastener kit
WARNING: If the unit is damaged in any way, do not proceed with the installation. Contact Span for further instructions.
2. Installation Requirements
Internet Connection
The Span Panel requires an internet connection to enable monitoring and control features, and to receive the latest software updates.
Be sure to register the product to establish communication with Span. Failure to do so may affect product performance or affect the
terms of the warranty. If a Wi-Fi signal is not available at the install location, establish an Ethernet connection between the Span Panel
and the customer’s router. Cellular LTE should only be relied on as a backup connection.
Required Equipment
● Branch circuit breakers for load and generation circuits. See Selecting Breakers.
● Main breaker (100–200 A) using SquareD type QOM2 breakers
● Conduit, conduit fittings, and SquareD A-Series threaded conduit hub suited to the installation
● Four #10 lag bolts or screws, 3 inches long (depending on attachment wall) for panel mounting, and washers (for use
between fasteners and enclosure)
● Conductors rated to minimum of 75°C. See table below and markings on breakers for acceptable wire gauge.
● Cable for communication between the Span Panel and solar inverter(s) (Minimum 300 V rated, shielded, twisted-pair,
copper, 22–16 AWG)
● Smartphone or tablet with Span Installer App for commissioning
Personal Protective Equipment (PPE) should be worn by all persons at the installation site and properly rated for residential applications.
Required Tools
● Torquing tools capable of 20–275 in-lbs (2.3–31.1 Nm)
● Allen bits (3/8-inch and 5/16-inch)
● Phillips, slotted, and square-drive driver
● Standard installation tools: wire cutters/strippers, multimeter, stud finder, level, tape measure, marker, and flashlight
NOTE: Verify that the site mechanical, electrical, and clearance requirements outlined in this document and the product
datasheet are compatible at the planned installation location.
NOTE: Install only compatible circuit breakers, hubs, conductors, and other accessories. Failure to do so may affect safety,
product performance, and may void the warranty.
NOTE: NEMA 3R rated conduit fittings are required for outdoor installations.
NOTE: For 22 kA short-circuit rating, branch breakers must be series-listed with the SquareD main breaker. Otherwise,
rating will be 10 kA.