APPENDIX A: CIRCUIT BREAKER COMPATIBILITY
Span has been evaluated per the UL Standard for Panelboards for use with the branch breaker types below.
Informational notes:
National Electric Code (NFPA 70) does not prohibit the use of different branch circuit breakers in panelboards provided it does
not violate the listing of any equipment. NEC article 110.3(B) states "Equipment that is listed, labeled, or both shall be installed and
used in accordance with any instructions included in the listing or labeling."
The standard for Molded-Case Circuit Breakers (UL 489) does not require listing circuit breakers for use in specific panel, nor
does this standard cover panelboards. Such testing is covered by the UL standard for Panelboards (UL 67), which does require
the panelboard to be listed with specific breaker types. Span is certified to the UL 67 standard via a Nationally Recognized
Testing Lab (NRTL) for use with the branch circuit breakers below. This is reflected in this Installation information as well as
marked on the product itself.
For additional information visit www.support.span.io
The Span Panel is compatible with the following Homeline circuit breakers from Square D:
General circuit breakers type HOM; 1-pole and 2-pole; rated 10-90 amperes; catalog numbers HOM followed by 110 to 290.
Tandem circuit breakers type HOMT; 1-pole; rated 10-30 amperes; catalog numbers HOMT followed by 1010 to 3020.
Quad tandem circuit breakers type HOMT; 1-pole and 2-pole; rated 15-50 amperes; catalog numbers HOMT followed by
1515215 to 2020250.
Quad tandem circuit breakers type HOMT; 2-pole; rated 15-50 amperes; catalog numbers HOMT followed by 215215 to 230250.
Combination arc fault circuit interrupter circuit breakers type HOM-CAFI; 1-pole and 2-pole; rated 10-20 amperes; with or
without plug-on neutral feature; catalog numbers HOM followed by 110 to 220; may be followed by P; followed by CAFI.
Ground fault circuit interrupter circuit breakers type HOM-GFI; 1-pole and 2-pole; rated 10-50 amperes; with or without plug-on
neutral feature; catalog numbers HOM followed by 110 to 250; may be followed by P; followed by GFI.
Ground fault equipment protection circuit breakers type HOM-EPD; 1-pole and 2-pole; rated 15-50 amperes; catalog numbers
HOM followed by 115 to 250; followed by EPD.
Dual function combination ground fault and arc-fault protection circuit breakers type HOM-DF; 1-pole; rated 10-20 amperes;
with or without plug-on neutral feature; catalog numbers HOM followed by 110 to 120; may be followed by P; followed by DF.
The Span Panel is compatible with the following circuit breakers from Eaton:
General circuit breakers type BR; 1-pole and 2-pole; rated 10-90 amperes; catalog numbers BR or BRH; followed by 110 to 290.
Duplex (tandem) circuit breakers type BD; 1-pole; rated 10-50 amperes; catalog numbers BD followed by 1010 to 5050.
Quadplex (tandem) circuit breakers type BQ and BQC; 1-pole and 2-pole; rated 15-50 amperes; catalog numbers BQ followed
by 215215 to 2502120.
Combination arc fault circuit interrupter circuit breakers type BR; 1-pole and 2-pole; rated 10-20 amperes; catalog numbers
BRC, BRN or BRL followed by 110 to 120; followed by AF or CAF.
Ground fault circuit interrupter circuit breakers type GFTCB and GFEP; 1-pole and 2-pole; rated 10-60 amperes; catalog
numbers BRN, GFTCB, BRHN, or GFTCBH followed by 110 to 260; may be followed by GF.
Ground fault equipment protection circuit breakers type GFEP; 1-pole and 2-pole; rated 15-50 amperes; catalog numbers BRN
or GFEP followed by 115 to 250; may be followed by EP.
Dual function combination ground fault and arc-fault protection circuit breakers type BR; 1-pole; rated 10-20 amperes; catalog
numbers BRN or BRAFGF followed by 110 to 120; may be followed by DF.
The Span Panel is compatible with the following circuit breakers from Siemens:
General circuit breakers type QP; 1-pole and 2-pole; rated 10-90 amperes; catalog numbers Q followed by 110 to 290; may be
followed by H.
Duplex (tandem) circuit breakers type QT; 1-pole; rated 10-30 amperes; catalog numbers Q followed by 1010 to 3030 may be
followed by NC.
Triplex (tandem) circuit breakers type QT; 1-pole and 2-pole; rated 10-30 amperes; catalog numbers Q followed by 21010 to
23030; followed by CT.
Quadplex (tandem) circuit breakers type QT; 2-pole; rated 15-40 amperes; catalog numbers Q followed by 21515 to 24040;
followed by CT2.