Install Manual

Span 1-00800-xx Installation Manual (rev. 2022-01-28) 14
Terminal Wire Gauge, Strip Lengths, and Torque Values
Terminal name
Wire gauge (AWG)
Wire strip length
Tool
Torque value in-lbs (Nm)
A
Main Breaker
See instructions on breaker
B
Main Neutral & Main GND terminal
#6 - 250 kcmil
1.25 in (32 mm)
3/8-in hex
250 - 275 (28.2 - 31.1)
C
Larger Neutral terminals
#14 - 1/0
0.75 in (20 mm)
5 mm
slotted
35 (4.0) for #14-10
40 (4.5 ) for #8
45 (5.1) for #6-4
50 (5.6) for #3-1/0
D
Smaller Neutral terminals &
GND terminal block
#14 - 4
0.5 in (12 mm)
5 mm
slotted
20 (2.3) for #14-10
25 (2.8) for #8
35 (4.0) for #6-4
E
Feed-through lugs (L1/L2)
#6 - 250 kcmil
1.25 in (32 mm)
5/16-in hex
250 - 275 (28.2 - 31.1)
NOTE: Torque circuit breaker terminals to values specified on the breakers.
NOTE: Terminals other than breaker terminals suitable for 60/75ÂșC AL/CU wire. Breaker terminals suitable for wire as
marked.
Span Panel AC Wiring