Instruction Manual

Form 925 (08.13) ©SOR Inc.
1/16
The RF Two-Wire Level Control produces a 7.5 mA (± 1.5 mA) or
14.5 mA (± 2 mA) current to indicate liquid presence/absence at the
sensor. A sensor attached to the control acts as an antenna to
transmit the process material level to the electronics.
The Failsafe Select switch determines the output of the unit when the
process is touching the probe. A green LED on the control indicates
7.5 mA (±1.5 mA) output. A yellow LED on the control indicates
14.5 mA (± 2 mA) output.
The RF Two-Wire level Control can be mounted with the sensor in
the process (integral units K housing), or up to 150’ (45m) from the
sensor in the remote configuration (R housing).
The RF Two-Wire level Control constantly monitors sensor integrity.
In the unlikely event of a sensor failure or remote electronic sensor
module failure, the red LED is lit and indicates 25.5 mA (±1.5 mA) output.
An optional timer (DT accessory) is available to delay the current change
from 0 seconds to 10 minutes. The delay timer provides added process
control, valuable for use in turbulent conditions. An optional adjustable
differential circuit (AD accessory) allows the user to select on and off at
different level points for the control.
DT and AD accessories may not be used on the same control unit.
General Instructions
Registered Quality System to ISO 9001
Design and
specifications are
subject to change
without notice.
For latest revision, go to
sorinc.com
Table of Contents
Pre-Installation Test ............................2
Installation ....................................... 3
Remote Cable Connection .....................4
Electrical Connection ...........................5
SOR RF Probe Grounding Scheme ...........6
Set Point and Sensor Monitor Calibration ..7
Adjustable Differential Calibration ...........9
Delay Timer Operation .........................9
Sensor Replacement ......................... 10
Circuit Board Replacement .................. 10
Troubleshooting ............................... 11
Dimensions ................................ 12-14
p
ut
.
g
e
s
e
a
t
NOTE: If you suspect that a product is
defective, contact the factory or the
SOR
®
Representative in your area for
a return authorization number (RMA).
This product should only be installed
by trained and competent personnel.
RF Two-Wire Level Control
with Sensor Monitor

Summary of content (16 pages)