Troubleshooting
Symptom Probable Cause
Float in actuated position but no output
signal.
No power supply.
Switch damaged. (Replace.)
Float in de-actuated position but still
receiving an output signal.
Switch damaged. (Replace.)
Control will not function when installed
but operates when removed from pro-
cess connection.
Inadequate float travel. Float travel
restricted by mounting nozzle. See
Mounting Requirements.
Liquid in vessel at the actuation level
but unit does not respond.
Leaky or collapsed float. (Replace.)
Liquid specific gravity too low.
Float stem bound up or dirty. (Clean.)
Part Number Description
3130-052 316SS Float Assembly
3130-091 W9 - SPST Hermetically Sealed Switch Capsule
3130-245 W1 - SPDT Hermetically Sealed Switch Capsule
3130-259
W1 - SPDT Switch/Conduit Connection Assembly (CK Option Only)
3130-107 L9 - SPST Hermetically Sealed Switch Capsule
3130-244 L1 - SPDT Hermetically Sealed Switch Capsule
3130-260
L1 - SPDT Switch/Conduit Connection Assembly (CK Option Only)
9227-028 MC Manual Check Assembly for 1 1/2” NPT Body*
9227-029 MD Manual Check Assembly for 1 1/2” NPT Body*
9227-024 MC Manual Check Assembly for 2” NPT Body*
9227-025 MD Manual Check Assembly for 2” NPT Body*
3130-040
20’ Remote Cable with two cable crimps, for use with MC or MD
accessory only.
Replacement Parts
* Unit must have originally been supplied with MC or MD option.