Clock Radio User Manual
Table Of Contents
- CP-UM-5093E-04.pdf
- SAFETY PRECAUTIONS
- Contents
- Chapter 1. GENERAL
- Chapter 2. NAMES & FUNCTIONS OF PARTS
- Chapter 3. MOUNTING
- Chapter 4. WIRING
- 4-1 Wiring Precautions
- 4-2 Compensating Lead
- 4-3 Terminal Connections
- 4-4 Layout of Terminals and Recommended Lead Draw-out Direction
- 4-5 Connecting the Ground and Power Supply
- 4-6 Wiring of Standard and Add-on Terminal Base
- 4-7 Connecting Inputs (analog inputs)
- 4-8 Connecting control outputs (outputs 1, 2)
- 4-9 Connecting auxiliary outputs (outputs 2, 3)
- 4-10 Connecting Event Output (relay output)
- 4-11 Connecting Time Event Output (open-collector)
- 4-12 Connecting External Switch (RSW) Input
- 4-13 Connecting for Communications
- 4-14 Isolating Inputs and Outputs
- Chapter 5. FUNCTIONS
- Chapter 6. OPERATION
- Chapter 7. PARAMETER SETUP
- Chapter 8. PROGRAM SETUP
- Chapter 9. TROUBLESHOOTING
- Chapter 10. SPECIFICATIONS
- Chapter 11. CALIBRATION
- Index

Chapter 9. TROUBLESHOOTING
9-7
■ Insertion/deletion of segments cannot be confirmed by pressing
FUNC
+
ENT
in pro-
gram setup state
The program setup cannot be changed.
The program being set up is being operated
(RUN. HOLD, FAST, END).
Not pattern item on programming map
Pattern item of non-set segment on program-
ming map
Cause Remedy
Set program parameter
P R T C setting to 0.
Reset the controller.
Move to pattern item on programming map.
Either move to already set up segment, or set up
segment.
■ Program deletion cannot be confirmed by pressing
FUNC
+
CLR
while entering pat-
tern items in program setup state
The program being set up is being operated
(RUN. HOLD, FAST, END).
Cause Remedy
Reset the controller.
The mode is not the READY mode.
The program of the currently selected pro-
gram No. is not set up.
The controller is in the constant-value opera-
tion mode.
The program is protected.
Key lock is enabled.
Cause Remedy
Reset the controller.
Select a program No. whose program is already set.
Set constant-value operation data
M .O D E setting to 0.
Set variable parameter
P R T C setting to 0.
Set variable parameter
L O C setting to 0, 1 or 3.
■ General reset is not applied by pressing
FUNC
+
CLR
+
DISP
in the basic display state
The mode is not the READY mode.
The mode is the MANUAL mode.
Program is protected.
Key lock is enabled.
Cause Remedy
Reset the controller.
Execute auto operation.
Set variable parameter
P R T C setting to 0.
Set variable parameter
L O C setting to 0.
■ The program cannot be copied by pressing +
PROG
in the basic display state