Datasheet
Index: WMGBPQM700
www.sonel.pl
export@sonel.pl
Sonel S.A.
Wokulskiego 11
58-100 Świdnica, PL
tel. +48 74 85 83 860
fax +48 74 85 83 809
POWER QUALITY ANALYZER
Possible measurements:
·
·
·
·
·
·
·
·
·
·
·
·
·
Measurements according to EN 50160,
values range ,
Crest factor for ,
,
reactive, distortion, including ,
Active, reactive, apparent energy,
Power factor
th
Up to 40 harmonics for voltage and current,
Total Harmonic Distortion (THD) for voltage and current
Short-term (P ) and long-term (P ) flicker,
ST LT
Unbalance of voltage and current,
Voltage L1, L2, L3,
- average, minimum, maximum and instantaneous , to 760 V, ability to work with voltage transformers
Current L1, L2, L3, N (four inputs)
- average, minimum, maximum and instantaneous values, measurement current with range to 3 kA (depends on used clamp), ability to work
with current transformers,
voltage and current
Frequency from 40 Hz to 70 Hz
Active, apparent power, the type of reactive power (capacitive, inductive)
Power recording:
- Budeanu method,
- IEEE 1459,
,
, cosφ, tgφ,
,
·
·
Current and voltage events registration including waveforms and RMS graphs half period,
ANALYZER MEASURES AND RECORDS ACCORDING TO THE IEC 61000-4-30 CLASS S STANDARD.
PQM-700
IP 65
·
·
·
power to the analyzer is supplied from tested mains (internal power supply) and is used in all types of networks from 64 V to 760 V,
with particular emphasis on measurements at low voltage poles, due to the ease of connection.
has an independent power supply socket, especially suited for voltage measurements for transformers and DC circuits.
built-in real-time clock
AN
AL
YZER MEASURES
AND RECORDS A
CCORDING
T
O THE IEC 61000-4-30
ST
AND
ARD
CLASS S
Operation:
-20...55°C-20...55°C