Datasheet

MPI-505
v.4
Measurement of short-circuit loop impedance Z in the RCD mode
L-PE
Measurement range acc. to IEC 61557: 0.5...1999 for a 1.2 m test leadΩ
Measurement of short-circuit loop impedance Z , Z , Z
L-PE L-N L-L
Measurement range acc. to IEC 61557: 0.13...1999Ω for a 1.2 m test lead:
Display
range
Resolution
Intrinsic error
0.00...19.99
20.0...199.9
200...1999
Ω
Ω
Ω
0.01
0.1
1
Ω
Ω
Ω
±(5% w.m. + 3 digits)
Nominal operating voltage Un / Un : 115/200V, 220/380V, 230/400V, 240/415V
L-N L-L
Operating voltage range: 100…264V (for Z i Z ) and 100…440V (for Z )
L-PE L-N L-L
Nominal power network frequency f : 50Hz, 60Hz
n
Operating frequency range: 45…65Hz
Maximal measurement current: 23A at 230V (10ms), 40A at 400V (10ms),
Verification of correctness of the PE terminal connection with a touch (for Z )
L-PE
Display
range
Resolution
Intrinsic error
0.00...19.99
20.0...199.9
200...1999
Ω
Ω
Ω
0.01
0.1
1
Ω
Ω
Ω
±(6% w.m. + 10 )digits
±(6% w.m. + 5 )digits
Does not trip RCD breakers of RCD current I 30mA
Δn
Nominal operating voltage U : 115V, 220V, 230V, 240V
n
Operating voltage range: 100…2 V
Nominal power network frequency f : 50Hz, 60Hz
n
Operating frequency range: 45…65Hz
Verification of correctness of the PE terminal connection with a touch probe
64
Display
range *)
Resolution
Intrinsic error
±(3% w.m. + 8 )digits
±(4% w.m. + 6 )digits
0...1999kΩ
2.00...19.99M
20.0...199.9MΩ
200...500MΩ
200...1000MΩ
200..1999MΩ
2.00...3.00GΩ
Ω
1k
0.01M
0.1MΩ
1MΩ
1MΩ
1MΩ
0.01GΩ
Ω
Ω
Measurement of insulation resistance
Measurement range acc. to IEC 61557-2:
for
for
for
for
10 10
Ω... Ω
U = 500V: 500kΩ...2GΩ
N
U = 1000V: 1MΩ...3GΩ
N
U = 0V: 0kΩ...500MΩ
N
U = 250V: 250k 1G
N
*) not exceeding the measurement range for a given voltage.
Range
Resolution
Intrinsic error
0.00...19.99
20.0...199.9
200...400
Ω
Ω
Ω
0.01
0.1
1
Ω
Ω
Ω
±(2% w.m. + 3 )digits
Low-voltage measurement of circuit continuity and resistance
Measurement of protective conductor continuity with current ±200 mA
Measurement range acc. to IEC 61557-4: Ω 0.12...400
The acronym “m.v.” stands for a “measured reference value”.
Measurements of RCD breaker parameters (operating voltage range 100…264 V):
RCD tripping test and measurement of t trip time (for the t measurement function)
A A
RCD type Multiplicity
Range Resolution Intrinsic error
General
Selective
0...300ms
0...150ms
0...40ms
0...500ms
0...200ms
0...150ms
1ms
±(2% w.m. + 2 digits)*
* - for I = 10mA and 0.5 I + 2% w.m. + 3 digits
Δn Δn
uncertainty is
Measurement of I RCD trip current for sinusoidal differential current
A
:
Nominal
current
Measurement
range
Intrinsic error
10mA
30mA
100mA
300mA
500mA
1000mA
3.3...10.0
9.0...30.0mA
33...100mA
90...300mA
150...500mA
330...1000mA
mA
± 5% I
Dn
0.1mA
1mA
Capability of starting the measurement from either positive or negative half-period of
forced leakage current
Nominal
current
Measurement
range
Intrinsic error
10mA
30mA
100mA
300mA
500mA
4.0...20.0
12.0...42.0mA
40...140mA
120...420mA
200...700mA
mA
±10% I
Dn
Resolution
Measurement
current
0.1mA
1mA
0.35 x I ...2
Dn Dn
.0 x I
0.35 x I ...1
Dn Dn
.4 x I
Measurement of I RCD trip current for pulsating unidirectional current:
A
Capability of measurement for either positive or negative half-periods of forced leakage
current
Maximal time of the measurement current flow is 3200 ms
Measurement
current
0.3 x I
Dn Dn
...1.0 x I
Resolution
Measurement voltage: 100 V, 250 V, 500 V and 1000 V
Detection of presence of voltage before the measurement
Discharge of the measured object after the measurement
Measurements of voltage on terminals +R , -R within the range of: 0…440 V
ISO ISO
Measurement current < 2 mA
Voltage on open terminals: 4…9V
Output current at R<2Ω: min. 200mA
Compensation of test lead resistance
Measurements for both polarities of current
Range
Resolution
Intrinsic error
0.00...199.9
200...1999
Ω
Ω
0.1
1
Ω
Ω
±(3% w.m. + 3 )digits
Measurement of resistance with low current
Voltage on open terminals: 4…9V, short-circuit current I :7mA
SC
Acoustic signal for a measured resistance value <30Ω + 50%
Compensation of test lead resistance
Indication of phase sequence
Indication of phase sequence: consistent, inconsistent
Power network U voltage range: 100…440 V
L-L
Displaying inter-phase voltage values
- WS-01 measurement triggering adapter with a UNI-Schuko plug
- 1.2 m red test lead terminated with banana plugs
- 1.2 m yellow test lead terminated with banana plugs
- 1.2 m blue test lead terminated with banana plugs
- USB data transfer cable
- red test probe with a banana socket
- yellow test probe with a banana socket
- blue test probe with a banana socket
- K02 yellow alligator clip
- K02 red alligator clip
- L4 case
- meter harness
- calibration certificate
- operating instructions
- SONEL CD
- warranty card
- 4 LR6 batteries
WAADAWS01
WAPRZ1X2REBB
WAPRZ1X2YEBB
WAPRZ1X2BUBB
WAPRZUSB
WASONREOGB1
WASONYEOGB1
WASONBUOGB1
WAKROYE20K02
WAKRORE20K02
WAFUTL4
WAPOZSZE2
- 5 m red test lead terminated with a banana plug
- 10 m red test lead terminated with a banana plug
- 20 m red test lead terminated with a banana plug
- WS-05 adapter with a UNI-Schuko plug
- AGT-16C adapter for 4-contact 3-phase sockets
- AGT-16P adapter for 5-contact 3-phase sockets
- AGT-16T adapter for industrial sockets
- AGT-32C adapter for 4-contact 3-phase sockets
- AGT-32P adapter for 5-contact 3-phase sockets
- AGT-32T adapter for industrial sockets
- AGT-63P adapter for 5-contact 3-phase sockets
- TWR-1J adapter for testing RCD breakers
- “SONEL Pomiary Elektryczne” program for creating reports
- “SONEL Schematic” prog. for creating drafts, electr. inst. schem.
- “SONEL PE Kalkulacje” program for creating measurement calc.
- official calibration certificate
WAPRZ005REBB
WAPRZ010REBB
WAPRZ020REBB
WAADAWS05
WAADAAGT16C
WAADAAGT16P
WAADAAGT16T
WAADAAGT32C
WAADAAGT32P
WAADAAGT32T
WAADAAGT63P
WAADATWR1J
WAPROSONPE5
WAPROSCHEM
WAPROKALK
Additional accessories of the meter:
Standard accessories of the meter: