Operation Manual

Functions and connections
20
Direct socket unit (push-button 1)
NOTE!
Swap connections (terminal 3 + 4) around if drive
is to be used with a side hinged door.
¾ Permissible cable cross-section: max. 1.5 mm².
2
3
4 5
6
1
Terminal 1 + 2 Transformer
Terminal 3 C-rail
Terminal 4 Chain
Terminal 5 + 6 Push-button contact (push-button 1)
CAUTION!
Use the contact (terminal 5 + 6) only for potential-free
normally closed contacts. External voltage may damage
or even destroy the control unit.
Early warning time (DIP 5)
The warning lamp starts to ash after push-button is pressed or the hand-
held transmitter is operated, before the drive starts. If the push-button is
pressed again or the hand-held transmitter operated during the 3 seconds,
the early warning period is ended prematurely.
The early warning time functions in conjunction with both internal lighting
and with a connected warning lamp.
DIP switch 5
OFF deactivated
ON activated, internal lighting and warning lamp with ash
for 3 seconds
Backjump (DIP 6)
NOTE!
With sectional doors, or doors with ceiling guides, you have
the option of enabling the backjump with DIP switch 6
in order to ofoad the operator and door mechanisms.
Easier operation of the emergency release.
This feature serves the purpose of supporting door and drive mechanism.
The drive mechanism moves briey back in a door OPEN direction once
it has reached the door CLOSED end position.
DIP switch 6
OFF deactivated
ON activated
Dened opening and closing
(DIP 7)
NOTE!
With this function, push-button 1/radio channel 1only opens
the door and push-button 2/radio channel 2 closes the door.
1
2
Push-button 1/radio channel 1 open and push-button 2/radio channel 2
close the door. This function can also be used with just 2 push-buttons
or with just a hand-held transmitter.
Requirement:
DIP switch 8 OFF
2 push-buttons connected (DIP switch 2 ON) or 2 hand-held transmitter
buttons programmed.
2
1
ON
3
4
5
6
87
6
DIP switch 7
OFF deactivated
ON activated