Operation Manual
19
General information
¾ If the DIP switch is set to OFF; all auxiliary functions are switched off.
¾ Cable length max. 10 m with terminal: 9 + 10, 11 + 12
¾ Cable length max. 30 m with terminal: 5 + 6, 7 + 8
Obstacle recognition (DIP 1, 2 + 3)
Drive behaviour upon opening the door
If the door meets an obstacle (force cut-off) or if the safety input
is interrupted (person triggering the light barrier), this is detected
by the drive system, depending on the position of the DIP switch 1.
DIP switch 1
OFF No response in the event of a safety input interruption.
In the event of a force cut-off, the door is halted.
ON Drive stops door
Drive behaviour upon closing the door
If the door meets an obstacle (force cut-off) or if the safety input
is interrupted (person triggering the light barrier), this is detected by the
drive system, depending on the position of the DIP switches 2 + 3.
DIP switch 2: Safety connection function
OFF Opener contact for light barrier
ON Push-button contact for push-button 2
(partial opening, dened opening and closing)
DIP switch 3: Behaviour of drive with door closing
OFF Drive stops and opens the door a little, reversal
ON Drive stops and opens the door completely
Connecting light barrier
¾ Permissible cable cross-section: max. 0.75 mm².
8
9
10 11
12
7
2
1
ON
DIP
3
4
5
6
8
7
+
NO
COM
NO
TX RX
COM
Terminal 7 + 8 Safety connection, only if DIP switch 2 OFF
Terminal 9 + 10 controlled DC 24 V, max. 0.1 A
• Terminal 9: DC 24 V
• Terminal 10: Earth
Settings: See chapter “Functions and connections – obstacle recognition
(DIP 1, 2 + 3)”.
Connecting push-button 2 (DIP 2)
¾ Permissible cable cross-section: max. 0.75 mm².
CAUTION!
Use the contact only for potential-free normally closed
contacts. External voltage may damage or even destroy
the control unit.
Connect push-button 2 if the functions described below are required:
• dened opening and closing
• partial opening
NOTE!
When using push-button 2 there is no further safety
connection available.
8
9
10 11
12
7
2
1
ON
DIP
3
4
5
6
8
7
Terminal 7 + 8
Connection for push-button 2, only if DIP switch 2 ON
Connecting warning lamp (DIP 4)
¾ Permissible cable cross-section: max. 0.75 mm².
8
9 10
11
12
7
2
1
ON
DIP
3
4
5
6
8
7
Terminal 11 + 12 uncontrolled DC 24 V (max. 34 Volt), max 1 A
DIP switch 4
OFF connected warning lamp ashes (control unit generates ashing)
ON door status indicator
• is lit when door is not closed
• is out when door is closed
Functions and connections