User's Manual

49
Installing the ERU
A water pipe by itself is not an acceptable building ground. It is acceptable only if
supplemented with a grounding rod and bonded to the central building ground
with a #6 AWG bond wire.
Mobile homes
For mobile homes, the electrical service panel or, if the service panel is inside the
trailer, the main electrical disconnect (the emergency disconnect switch outside
the trailer), must be within sight of and within 9 m (30 feet) of one of the mobile
home’s walls. If none of the above-mentioned grounds are available, or if the
distance is greater than 9 m (30 feet), a 2.5-m (8-foot) grounding rod must be
driven into the ground as close as possible to the ground block. The grounding
rod must be bonded to the metal frame of the mobile home, or to a ground
terminal with a #12 AWG copper bond wire.
Burying the cable
Depending on the location of the ERU and the ground block, you may choose to
route the coaxial cable underground.
If you choose to bury the coaxial cable, pay special attention to the cable type.
When normal coaxial cable is buried, its outer cover decays in the soil, and the
cable’s life is shortened. Cables that are suitable for burial have a special outer
cover that resists breakdown. Some of these cables also have a special coating on
their ground shields. This coating resists corrosion if water gets into the cable.
Protecting the cable from damage
If you are routing the cable above the ground, use cable clips to secure it to a wall
or surface. Make sure you route the cable in an area where people or animals are
not likely to come in contact with the cable.
Prevent moisture penetration by using weatherproof connectors or by sealing any
connection that is exposed to the elements. Drip loops provide additional
protection by preventing moisture from traveling down the cable and entering
the connection.