User's Manual Part 1

56 Part ######A revision 00a-DRAFT March 29, 2006
Macro Base Station Installation Procedures (NPM-1000)
6 Connect the compression lug on the main ground cable to one of the two ground terminals, as shown in
Figure 4.6. Use a 1/4-inch hex nut with a 1/4-inch split-lock washer when securing the cable. Torque
each 1/4-inch hex nut to 78 inch-pounds.
Figure 4.6
Ground Terminals on the PDP
7 Connect the frame ground cable to the second ground terminal on the PDP using a minimum of #6 AWG
stranded copper wire.
8 Connect the other end of the frame ground cable directly to the top-left corner (when viewed from behind)
of the rack:
i Punch a hole in the grounding tape for each compression lug screw location.
ii Attach the compression lug using two 5/16-inch hex screws with locking and external tooth washers.
9 Repeat steps 1 to 8 for the second rack.
10 Dress and label the ground cables according to the standards and requirements of your site.
00281
Ground Terminals