Chapter 2: Site Preparation
Base Station Circuit Breaker Current Loads
Each rack contains a power distribution panel (PDP). The PDP has up to 16 circuit breakers (CBs).
Each breaker switch controls the power to a specific component. Individual components can be
powered off by setting the appropriate breaker switch to the OFF (down) position.
Table 2.13 shows the maximum current loading of the circuit breakers in the RFSS and radio rack
PDPs.
Circuit Breaker RFSS Rack PDP Radio Rack PDP
CB 01 10A 10A
CB 02 30A 30A
CB 03 30A 30A
CB 04 30A 30A
CB 05 30A 30A
CB 06 30A 30A
CB 07 30A 30A
CB 08 30A 30A
CB 09 30A 30A
CB 10 30A 30A
CB 11 30A 30A
CB 12 30A 30A
CB 13 30A 30A
CB 14 10A 10A
CB 15 — 2.5A
CB 16 — —
Table 2.13
Circuit Breaker Current Loads (+24V)