User Manual

66 Part 003609A revision 01 December 16, 2002
Amosphere NPM Installation Procedures (WCS)
Figure 4.7
Main and Return Power Terminals
10 Ensure the main and return power cables are connected to the main power supply
correctly by performing a continuity test on each cable.
11 Dress and label the main and return power cables according to the standards and
requirements of your site.
NOTE: Ensure that the main and return power cables are tied
in a manner that minimizes the potential for creating
electromagnetic fields. When tied together, the main and return
power cables should be arranged in an alternating order.
12 Repeat steps 1 to 9 for the second rack.
13 Reattach the rear cover to each rack’s PDP using four #2 Phillips screws. Torque
each screw to 12 inch-pounds.
00282
+24V Main Power
Terminals
Return Power
Terminals