Instruction Manual

UM0039_Ai-LB 5k_EN_V01_0223 28
6. Transportation and Storage
Transportation
It is forbidden to encounter serious vibration and shock during transportation.
Storage
If the system is not placed to use, the system must be properly stored. Otherwise, if any issues, AISWEI shall not
be liable.
It should be stored in 60% SoC status.
It should be stored at ventilation environment, Temp. < 35 °C, ROH <65%.
It should be stored avoiding humid condition.
It should be stored in place where they can be monitored by professionals.
NOTE
A proper inspection shall be conducted every 3 months, to ensure no over-discharge of the battery (SoC is long
time less than 0%) occurs. At over-discharge status, the battery would behavior as:
The battery could not start-up when turning the power switch to the ON position;
The battery output voltage is less than 40V when turned on;
Indicators are off and battery can not communicate to the upper computer via RS485/USB converter.
Please contact the technical person where you purchase the battery from immediately once the above abnormal
issues occur. And actions in terms of re-charging the battery (to the SoC 50%) is required before the field
installation.
7. Disclaimer
It should be noted that supplier shall not be liable if any necessary materials are added to this users manual
without further inform of customers.