Solis_Manual_75_100K_5G_USA_V1.4

8. Troubleshooting
Alarms
Cause Solution
INI-FAULT:
Initialization
Protection
Master and Slave DSP
have different values
Reset Inverter
DC switch OFF
Wait until all lights/LCD turn off
DC switch ON
Replace inverter
OV-T EM:
Temperature
Protection
Inverter detects high
ambient temperature >60C
Inspect installation
Check heatsink for obstructions/ventilation
Is inverter in direct sunshine
Measure ambient temperature near inverter
If temp is in range replace inverter
PV ISO-P RO
01/02:
Ground
Protection
Inverter detects low DC
insulation resistance
Inspect installation
Reset inverter
Note weather conditions when alarm occurs
Measure insulation resistance
If normal, measure in SAME weather as alarm
Physically check cables
Replace inverter
ARC-FAULT
Inverter detects arc
in DC circuit
Inspect installation
Check cable with string tester
Physically check cables
Inspect panel junction boxes
Inspect cable connections
Reset inverter
Replace inverter
Table 8.1 Fault messages and descriptions
Screen OFF
with DC applied
Inverter internally
damaged
Do not turn off the DC switches as it may
damage the inverter.
Please wait for sunset and confirm the string
current is less than 0.5A with a clip-on ammeter
and then turn off the DC switch. String current
above 0.5A is under load.
Note: Damage due to wrong connections or fire
caused by removing string wires or opening
fuse holders under load is not covered in the
device warranty.
Reve-DC
Please check the inverters’ PV string polarity,
if there are strings reversely connected wait for
the night when the solar irradiance is low and the
PV string current down below 0.5A. Turn off the
two DC switchs and fix the polarity issue.
If string polarity is correct, please confirm that all
the PV strings have the same number of modules.
If not, please modify the system configuration.
One of the DC string is
reversely connected
OR different number of
modules are connected
to the string inputs
(Threshold varies between
different conditions)
.68. .69.
Dimensions (W*H*D)
Weight
1065*567*344.5 (mm) / 41.9*22.3*13.5 (inch)
3/PE~480
Max. DC input voltage (Volts)
MPPT voltage range (Volts)
Full load MPPT voltage range (Volts)
Max. input current (Amps)
MPPT number/Max input strings number
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
Max.efficiency
EU efficiency
MPPT efficiency
Model
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission
Cooling concept
Max.operation altitude
AC connection
Compliance
DC connection
1000
8*26
8*40
8/16
0.8leading~0.8lagging
60
98.7%
98.3%
99.5%
Transformerless
2W
-13...140 / -25...+60
0~100%
Display
Communication connections
Warranty
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
MC4
OT Terminal connectorsMax.185mm²
LCD,2x20Z
RS485, Optional: Wifi, PLC, Ethernet
10 years standard (extend to 20 years)
600
75000
75000
75000
90.2
THDi (at rated output power)
<3%
Start-up voltage (Volts)
Max short circuit input current (Amps)
Rated DC voltage (Volts)
Rated grid frequency (Hertz)
180...1000
195
UL 1741, I EEE 1547, UL 1699B, UL 1998,
FCC, UL 1741SA, California Rule 21
Solis-75K-5G-US
85kg
TYPE 4X
65dB(A)
Intelligent redundant cooling
13120ft / 4000m
550...850
9. Specifications