8. Troubleshooting 8. Troubleshooting
Alarms
Cause Solution
•  Input voltage low/missing
•  Polarity reversed
•  Main board damaged
No Information 
(Blank Screen)
 Test – DC switch OFF
•  Check PV connections
•  Check polarity
•  Check voltage >860V
 Test – DC Switch ON
•  Check voltage >860V
•  If DC voltage is “0” replace inverter
Initializing 
(Inverter stuck 
in this mode)
•  Inverter is waiting for 
 driving signal
 Test – DC switch OFF
•  Check PV connections
•  Check polarity
•  Check voltage >860V
 Test – DC Switch ON
•  Check voltage >860V
•  A cable may have been damaged or loosened 
 in shipping replace inverter
OV-G-V: Over 
Grid Voltage
•  Inverter detects grid 
 voltage as too high
 Test – DC switch OFF
•  Check AC at the inverter 
•  If AC measures high, adjust upper limit with 
 permission from utility
 Test – DC Switch ON, full power
•  Check AC at inverter test points
•  Compare with LCD
•  If AC measures high, cables between inverter 
 and interconnect are too small
•  Check ampacity and voltage drop calculations
UN-G-V: Under 
Grid Voltage 
•  Inverter detects grid 
 voltage as too low
 Test – DC switch OFF
•  Check AC at the inverter test points
•  If AC measures low, adjust lower limit with 
 permission from utility
•  Check LCD voltage reading, may be a bad 
 measurement circuit
 Test – DC Switch ON
•  Check grid standard
•  Replace inverter
UN-BUS: DC 
BUS voltage is 
too low
•  Inverter detects low DCV 
 on internal bus
 Test 
•  Measure DC and AC voltages
•  Compare with LCD
•  Replace Inverter
•  Internal damage
•  Wire came loose during shipping
.66. .67.
•  Inverter detects grid 
 instability, internal fault 
 current high
GRID-INTF: 
Grid unstable
 Test – With DC Switch OFF
•  Measure AC voltage
•  Test AC line for THD
•  Test – With DC Switch ON
 Test AC line for THD
•  Multiple inverters/turn one off
•  Impedance matching adjustment or box
•  Internal damage
•  Wire came loose in shipping
Alarms
Cause Solution
•  Inverter detects grid 
 Frequency as too high
OV-G-F: Over 
Grid Frequency
 Test – DC switch OFF
•  Check frequency at the inverter test points
•  If Frequency measures high, adjust upper 
 limit with permission from utility
•  Check LCD reading, may be a bad 
 measurement circuit
 Test – DC Switch ON
•  Check grid standard
•  Replace inverter
NO-GRID
•  Inverter does not 
 detect the grid
 Test – DC switch OFF
•  Check AC at the inverter test points
•  L-L, L-GND
•  Check LCD reading, may be a bad 
 measurement circuit
 Test – DC Switch ON
•  Check grid standard
•  Replace inverter
OV-DC: DC 
voltage is too 
high
•  Inverter detects High DCV
 Test – DC switch OFF
•  Check DC at the inverter test points
•  If DCV is high, too many panels in the string
 Test – DC Switch ON
•  Check LCD reading, may be a bad 
 measurement circuit
•  Replace inverter
OV-BUS: DC 
BUS voltage is 
too high
•  Inverter detects High 
 DCV on internal bus
 Test 
•  Measure DC and AC voltages
•  Compare with LCD
•  Replace Inverter
•  Internal damage
•  Wire came loose during shipping