Solis_Manual_75_100K_5G_USA_V1.4
6. Normal operation6. Normal operation
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
2. Volt-Watt (Not Required)
Description: Inverter will change the active output power based on voltage change.
Note: This Setting is NOT required by UL1741SA Standards.
3. Volt-Var (Default)
Description: Inverter will change the reactive output power based on voltage change.
Q1,cap
Q2=Q3= 0
Q4,ind
V1 V2 Vnom V3 V4
Figure 6.21 Volt- VAR curve for Q(V)
Default Settings for UL1741SA:
Q1: (0-60%) Default +30% Q4: (-60%-0%) Default -30%
Rated 480V Grid
V1:(221-279V) Default 242V V2: (221-279V) Default 273V
V3:(277-320V) Default 281V V4: (277-320V) Default 305V
Figure 6.22 Volt-VAR
Voltage1: 242V
Voltage2: 273V
1.NULL
Description: Inverter is not under any working mode.
.49..48.
YES=<ENT> NO=<ESC>
Power Factor: + 1. 00
Figure 6.23 Fixed-PF Figure 6.24 PF Range
4.Fixed-PF
Description: Inverter will output power with fixed power factor.
Setting Range: -0.8 to +0.8
Default value is PF = 1
5. Reac-power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by UL1741SA Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6. P-factor (Not Required)
Description: Inverter will change power factor based on changing output power.
Note: This Setting is NOT required by UL1741SA Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.