6. Normal operation6. Normal operation
6.7.5 Power Control
Active and reactive power can be set through power setting button.
There are 5 item for this sub menu:
1. Set output power
2. Set Reactive Power
3. Out_P With Restore
4. Rea_P With Restore
5. Select PF Curve
This function is applicable by maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6.7.6 Calibrate Energy
Maintenance or replacement could clear or cause a different value of total energy. Use this
function could allow user to revise the value of total energy to the same value as before. If
the monitoring website is used the data will be synchronous with this setting automatically.
(see Figure 6.20).
Figure 6.20 Calibrate energy
YES=<ENT> NO=<ESC>
Energy:0000000kWh
Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the
ENTER key to execute the setting. Press the ESC key to return to the previous menu.
6.7.7 Special Settings
This function is applicable by maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
.47..46.
6.7.8 STD Mode Settings
1. Working Mode Set
2.Power Rate Limit
3.Freq Derate Set
4.10mins Voltage Set
5.Power Priority
6.Initial Settings
7.Voltage PCC Set
8.Freq-Watt
Selecting “STD Mode. Settings displays the sub-menu shown below:
This section is applicable to maintenance personnel only.
Solis US version inverters have Seven working modes:
1. NULL
2. Volt-watt
3. Volt-Var
4. Fixed-PF
5. Reac-power
6. Power-PF
7. VgWatt-UL
Based on UL1741SA, working mode 1,3,4,7 can be used by grid operator.
6.7.8.1 Working Mode Set
6.7.8.1.1 With UL Standard selected
There are TWO situations with different grid standards selected.
NOTE
The following modes are for "UL-480V-A".