Solis_Manual_75_100K_5G_USA_V1.4
6. Normal operation6. Normal operation
OV-G-V1: 236---335V
OV-G-V1-T: 0.1---9S
OV-G-V2: 248---341V
OV-G-V2-T: 0.1---1S
UN-G-V1: 173---236V
UN-G-V1-T: 0.1---9S
UN-G-V2: 132---219V
UN-G-V2-T: 0.1---1S
Startup-T: 10-600S
OV-G-F1: 60.2-63Hz
OV-G-F1-T: 0.1---9S
OV-G-F2: 61-63Hz
OV-G-F2-T: 0.1---9S
UN-G-F1: 57-59.5Hz
UN-G-F1-T: 0.1---9S
UN-G-F2: 57-59Hz
UN-G-F2-T: 0.1---9S
Restore-T: 10-600S
Table 6.2 Setting ranges for User-Def
NOTE
The initial value of the User-Def standard is for reference only. It does
not represent a correct value suitable for use.
Table 6.3 Baseline Inverter Settings
Setting value
Vup-Limit1
528<V<576
Time1
1S
Vup-Limit2
V≥576
Time2
0 16S.
Vdw-Limit1
288≤V<422
Time1
2S
Vdw-Limit2
V<288
Time2
0 16S.
Fup-Limit1
60.5Hz<F<62Hz
Time1
2S
Fup-Limit2
Time2
Fdw-Limit1
Time1
Fdw-Limit2
Time2
F> 2Hz6
0 16S.
57Hz<F<59.5Hz
2S
57Hz<F
0 16S.
480V Rated (L-N)
305<V<333
1S
V≥333
0 16S.
166≤V<244
2S
V<166
0 16S.
60.5Hz<F<62Hz
2S
F> 2Hz6
0 16S.
57Hz<F<59.5Hz
2S
57Hz<F
0 16S.
480V Rated (L-L)
.45..44.
6.7.2 Grid ON/OFF
This function is used to start up or stop the power generation of Solis Three Phase
Inverter (see Figure 6.18).
Grid ON
Grid OFF
Figure 6.18 Set Grid ON/OFF
Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key
to save the setting. Press the ESC key to return to the previous menu.
These two functions are applicable by maintenance personnel only, wrong
operation will prevent the inverter from working properly.
6.7.3 Clear Energy
Clear Energy can reset the history yield of inverter
6.7.4 Reset Password
This function is used to set the new password for menu “Advanced info.” and “Advanced
information” (see Figure 6.19).
Figure 6.19 Set new password
YES=<ENT> NO=<ESC>
Password: 0000
Enter the right password before set new password. Press the DOWN key to move the cursor,
Press the UP key to revise the value. Press the ENTER key to execute the setting.
Press the ESC key to return to the previous menu.