Solis_Manual_RHI-1P(5-10)K-HV_USA_V1,1

5. Operation 5. Operation
Settings
Meter Select
2015-02-23 19 35
5.6.5.1 Meter Select
Figure 5.36 Storage Energy Set
1Ph Meter
Meter Type:
Y E S =< E N T > N O = < E S C >
E S C
U P
D O W N EN T
The setting is used to select the meter type based on the actual configuration.
NOTE:
Select "1Ph Meter" to be compatible with the meter that comes with the
inverter package.
The "3Ph Meter" is not available yet which is reserved for future development.
There are two optional modes:
1. Time Charging 2. Off-grid Mode
The default mode is called "AUTO" mode (which is not shown and can not be selected).
The "AUTO" mode logic is: Store excess PV energy into the battery and then use it to
support loads instead of exporting to the grid. (Maximize system self-consumption rate).
To change back to the default mode, simply set all the other modes as OFF.
Settings
Storage Mode Select
2015-02-23 19 35
TimeCharging
Mode:
Figure 5.37 Storage Mode Select
5.6.6.2 Storage Mode Select
.40. .41.
Settings
TimeCharging
2015-02-23 19 35
Optimal Income
I_Charge
HH
T_Charge
Stop
050.0A
22
T_Discharge 08
N EX T = < E N T > D O N E = < E S C >
I_Discharge
050.0A
MM
00
00
---
---
Total Time
Total Time
HH
08
22
MM
00
00
HH
10
14
MM
00
00
Figure 5.38 Time Charging
Time Charging Mode:
"Optimal Income" is the switch to turn on/off the Time Charging Mode.
Customer can define the charge/discharge current as well as when to charge/dischage the battery.