5. Operation 5. Operation
Default Settings for UL1741SA:
Rated 240V Grid
V1:less than V2
V2:less than Vstart
V3 (Vstart): (240-288V) Default264V
V4 (Vstop): (264-312V) Default 288V
P1:100% P2:100% P3: 100% P4:0%
Rated 208V Grid
V1:less than V2
V2:less than Vstart
V3 (Vstart): (208-250V) Default229V
V4 (Vstop): (229-270V) Default 250V
P1:100% P2:100% P3: 100% P4:0%
Figure 5.46 Vgwatt-UL
2015-02-23 19 35
Voltage1:
P-Limit1:
Voltage2:
P-Limit2:
Voltage3:
210.0V
100%
236.0V
100%
264.0V
P-Limit3:
Voltage4:
100%
288.0V
P-Limit4: 000%
S ET = < E N T > D ON E= < E S C >
Volt-Var
5.6.6.1.2 With Rule21 Standard selected
NOTE:
The following modes are for "R21P3-240", "R21P3-24A".
Solis US version inverters have Ten working modes:
1. NULL 2. Volt-watt 3. Volt-Var 4. Fixed-PF 5. Reac-power 6. Power-PF 7. VgWatt-UL
Based on Rule21, working mode 1,2,3,4 can be used by grid operator.
NOTE:
The other three working mode"P1-V-Watt","P1-V-Var" and
"P1-V-P&V-Q" are NOT applicable for settings.
1.NULL (Mode Reset)
Description: Inverter is not under any working mode.
2. Volt-Watt
Description: Inverter will change the active output power based on voltage change.
Note: This is the Volt-Watt Setting for Rule21 Standards.
Figure 5.47 Volt- Watt characteristic
No Real Power
Production Zone
0% 106% 108% 110%
Real Power
Reduction Zone
Full Power Production
Capabilities Zone
50%
100%
Active Power as % of
Nameplate
% Voltage
Rated 240V Grid
V1:less than Vstart
V2 (Vstart): (240-288V) Default 254V
V3 (Vstop): (240-288V) Default 264V
V4: larger than Vstop
P1:100% P2:100% P3: 0% P4:0%
Rated 208V Grid
V1:less than Vstart
V2 (Vstart): (208-250V) Default 221V
V3 (Vstop): (208-250V) Default 229V
V4: larger than Vstop
P1:100% P2:100% P3: 0% P4:0%
Default Settings for Rule21 Standards:
.46. .47.
NOTE:
Parameter Accuracy:
Voltage:1%; Current:1%; Frequency:0.06Hz; Power:4%; Time:0.12s; PF:0.01.