Solis_Manual_RHI-1P(5-10)K-HV_USA_V1,1
Default Settings for UL1741SA:
Q1: (0-60%) Default +30% Q4: (-60%-0%) Default -30%
Rated 240V Grid
V1:(192-240V) Default 210V V2: (192-240V) Default 236V
V3:(240-288V) Default 243V V4: (240-288V) Default 264V
Rated 208V Grid
V1:(166-208V) Default 182V V2: (166-208V) Default 205V
V3:(208-240V) Default 211V V4: (208-240V) Default 229V
5. Operation 5. Operation
Figure 5.42 Volt-Var
2015-02-23 19 35
Voltage1:
Voltage2:
Voltage3:
210.0V
236.0V
243.0V
Voltage4:
264.0V
S ET = < E N T > D ON E= < E S C >
4.Fixed-PF
Description: Inverter will output power with fixed power factor.
Setting Range: -0.8 to +0.8 Default value is PF = 1
Figure 5.43 Fixed-PF
2015-02-23 19 35
Power Factor: +1.00
.44. .45.
Volt-Var
Fixed-PF
Y E S =< E N T > N O = < E S C >
Figure 5.44 PF Range
0,6
0,6
1,0-1,0
P/Pn
under-excited
Q/Pn
under-excited
over-excited
over-excited
III
IV
III
-0,2
5. Reac-Power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by UL1741SA Standards.
NOTE:
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6. P-Factor (Not Required)
Description: Inverter will change power factor based on changing output power.
Note: This Setting is NOT required by UL1741SA Standards.
7.VgWatt-UL
Description: Inverter will change the active output power based on voltage change.
Note: This is the Volt-Watt Setting for UL1741SA Standards.
100% of
Input
Power
Vmin Vnom Vstart Vstop Vmax
AC Volt
0
Figure 5.45 Volt- Watt characteristic
NOTE:
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
Leading:
+030%
Leading:
-030%