Solis_Manual_RHI-1P(5-10)K-HV_USA_V1,1
5. Operation 5. Operation
This function is used to select corresponding grid standards.
Please refer to the actual LCD setting for the grid standard options.
Figure 5.25 Select Standard
5.6.1 Select Standard
Settings
Select Standard
2015-02-23 19 35
Y E S =< E N T > N O = < E S C >
UL-240V
Select Standard:
Press "UP" and "DOWN" to go through the list.
Press "ENT" to check the parameters, press "ENT" again to select the standard.
This function is used to start or stop the generation of the inverter (see Figure 5.26).
Figure 5.26 Set Switches
5.6.2 Switches
SettingsSwitches
2015-02-23 19 35
ON
OFF
Y E S =< E N T > N O = < E S C >
STOP
This section is used to select the corresponding battery and set the battery wakeup function.
Figure 5.27 Battery Control
5.6.3 Battery Control
SettingsBattery Control
2015-02-23 19 35
BatterySelect
BatteryWakeup
Y E S =< E N T > N O = < E S C >
This product is compatible with the following battery modules:
5.6.3.1 Battery Select
BYD
Brand
Select"B-BOX"
Setting
Select"LG Chem"
Battery-BOXH5.0/7.5/10 (UL 9540)
Model
RESU10H (UL 9540)
If hybrid inverter is not connected to a battery, then select "No Battery" to avoid alarms.
For above compatible battery modules, Only two parameters need to be defined:
* OverDischg SOC (10%~40%, default 20%)
--Inverter will not discharge the battery when the OverDischg SOC is reached.
Battery self-discharge is unavoidable,SOC may go lower than the limit if the battery
can't get charged for a long period of time.
* ForceCharge SOC (5%~OverDischg SOC, default 10%)
--To prevent the battery going into sleep mode, when the ForceCharge SOC is reached,
inverter will charge the battery using the power from either PV or Grid.
.34. .35.
Press the UP/DOWN keys to select the standard (UL-240V, UL-208V, R21P3-240,
R21P3-208, ISONE240, ISONE208, MEX-CFE , User-Def, etc.).
Press the ENTER key to confirm the setting.
Press the ESC key to cancel changes and return to previous menu.
There are 6 settings for USA and CSA market, UL-240V, UL-208V, R21P3-240, R21P3-208,
ISONE240 and ISONE208. The default grid setting is UL-240V.
NOTE:
ON: AC Relay is ON.
OFF: AC Relay is OFF.
Stop: AC Relay is ON, but power generation.
LG Energy
Solution
Soluna
Select"Soluna"
15K PACK HV