User's Manual

Confidential & Proprietary 7/39
- A readyily accessible disconnect device shall be incorporated external to the equipment.
- This power of this system shall be supplied through wiring installed in a normal building.
If powered directly from the mains distribution system, it shall be used additional protection, such as
overvoltage protection device
- Only 50 ohm rated antennas, cables and passive equipment shall be used with this remote. Any
equipment attached to this device not meeting this standard may cause degradation and unwanted
signals in the bi-directional system. All components connected to this device must operate in the
frequency range of this device.
- Only 50 ohm rated antennas, cables and passive components operating from 150 - 3 GHz shall be used
with this device.
- The head end unit must always be connected to the Base Station using a direct cabled connection.
This system has not been approved for use with a wireless connection via server antenna to the base
station.
- Round terminals located on the side of a 1 mm2 (16 AWG) or more wires Using permanently
connected to earth.(green/yellow color)
- The following notice: "The Manufacturer's rated output power of this equipment is for single carrier
operation. For situations when multiple carrier signals are present, the rating would have to be reduced
by 3.5 dB, especially where the output signal is re-radiated and can cause interference to adjacent band
users. This power reduction is to be by means of input power or gain reduction and not by an attenuator
at the output of the device."
- Part 90.635 requirement
Antennas must be installed in accordance with FCC 90.635. With 17 dBi gain antennas the height of the
antenna above average terrain (HAAT) must not exceed 763 m. For different gain antennas refer to the
relevant rules.
- Prior to equipment use the service must be registered with the FCC. This can be done through the
FCCs website at https://signalboosters.fcc.gov/signal-boosters/.