MODEL TRC
TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS
TRC800
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airow Range: 250-925 CFM
AHRI 1060 Certied Core: One L125-00
Airow Rating Points (for AHRI): 750 CFM and 563 CFM
Number Motors: Two direct drive blower/motor packages
V Hz Phase
FLA
(per motor)
Min. Cir.
Amps
Max. Overcurrent
Protection
Device
115 60 Single 9.0 20.3 25
208-230 60 Single 4.5 10.1 15
Standard Features: Non-Fused Disconnect
24 VAC Transformer/Relay Package
Filters: Two total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 211 lbs (unit), 300 lbs (shipping weight, on pallet)
Shipping Dimensions: 62” L x 48” W x 40” H
* At AHRI 1060 standard conditions
(see certied data on page 69 for core components.)
LISTED
DUCTED HEAT
RECOVERY VENTILATOR
89S5
Specications
Performance
Motor HP External Static Pressure (Inches Water Column)
Phase 0.0 0.25 0.5 0.75 0.9 1.25 1.5
0.75 970 CFM 925 CFM 860 CFM 795 CFM 750 CFM 635 CFM 480 CFM
Single Phase 1,490 Watts 1,375 Watts 1,270 Watts 1,160 Watts 1,090 Watts 950 Watts 825 Watts
Airow Performance
Note: Watts is for the entire unit (two motors).
250
40
Effectiveness (%)
80
60
500 1,000750
CFM
Sensible
Winter Total
Summer Total
MODEL TRC