Specification Sheet

S&P USA: www.solerpalau-usa.com S&P Canada: www.solerpalaucanada.com
37
Motor
HP
RPM
Static Pressure in Inches w.g.
0 .125 .25 .375 .5 .625 .75 .875 1 1.25 1.5 1.75
STXD
3/4 HP
1650 RPM
1300
CFM 2658 2554 2452 2347 2226 2085 1938 1790 1578 - - -
BHP 0.30 0.32 0.35 0.37 0.39 0.42 0.44 0.46 0.46 - - -
Sones 15.5 15.0 14.5 14.1 13.6 13.2 12.9 12.5 12.3 - - -
1350
CFM 2760 2660 2562 2462 2351 2220 2078 1943 1790 - - -
BHP 0.34 0.36 0.38 0.41 0.44 0.46 0.48 0.50 0.52 - - -
Sones 16.5 16.0 15.6 15.2 14.7 14.4 14.0 13.6 13.3 - - -
1400
CFM 2862 2766 2671 2575 2473 2352 2218 2082 1947 1410 - -
BHP 0.38 0.40 0.42 0.45 0.48 0.50 0.52 0.55 0.57 0.54 - -
Sones 17.6 17.1 16.6 16.2 15.8 15.4 15.1 14.7 14.4 13.8 - -
1450
CFM 2965 2871 2780 2688 2592 2480 2354 2222 2096 1745 - -
BHP 0.42 0.44 0.47 0.49 0.52 0.55 0.57 0.60 0.62 0.63 - -
Sones 18.7 18.2 17.8 17.3 16.9 16.5 16.2 15.8 15.5 14.9 - -
1500
CFM 3067 2977 2888 2799 2708 2606 2488 2362 2235 1968 - -
BHP 0.46 0.49 0.51 0.54 0.57 0.60 0.62 0.65 0.68 0.71 - -
Sones 19.8 19.3 18.9 18.5 18.0 17.6 17.3 16.9 16.6 16.0 - -
1550
CFM 3169 3082 2996 2910 2823 2729 2618 2499 2375 2127 - -
BHP 0.51 0.53 0.56 0.59 0.62 0.65 0.68 0.70 0.73 0.78 - -
Sones 20.7 20.3 19.8 19.4 18.9 18.6 18.2 17.9 17.5 16.9 - -
1600
CFM 3271 3187 3103 3020 2936 2848 2746 2634 - - - -
BHP 0.56 0.59 0.61 0.64 0.68 0.71 0.73 0.76 - - - -
Sones 21.6 21.2 20.7 20.3 19.9 19.5 19.1 18.8 - - - -
1650
CFM 3374 3291 3210 3130 3049 2965 - - - - - -
BHP 0.61 0.64 0.67 0.70 0.73 0.76 - - - - - -
Sones 22.5 22.1 21.6 21.2 20.8 20.4 - - - - - -
STXD
1-1/2 HP
1725
RPM
1750
CFM 3997 3900 3806 3717 3628 3535 3436 3336 3237 3027 2781 2492
BHP 0.78 0.82 0.86 0.90 0.94 0.97 1.01 1.04 1.08 1.13 1.18 1.21
Sones 26.2 25.7 25.2 24.7 24.5 24.2 23.8 23.4 23.0 22.3 21.9 21.6
MODEL STXD & STXDe
DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER
MODEL STXD & STXDe
DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER
SIZE 15 - 3/4 & 1 HP
R
®
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
AIR
PERFORMANCE
SOUND
and
S&P USA Ventilation Systems, LLC.,
Div. of Soler & Palau Ventilation Group,
certies that the Models STXD shown
herein are licensed to bear the AMCA
Seal. The ratings shown are based
on test and procedures performed in
accordance with AMCA Publication 211
and AMCA Publication 311 and comply
with the requirement of the AMCA
Certied Ratings Program.
Performance certied is for installation type A-free inlet, free outlet.
Performance ratings do not include the e󰀨ects of birdscreen in the airstream.
The sound ratings shown are loudness values in fan sones @ 5' (1.5m) in a hemispherical free eld calculated per AMCA Standard 301. Values shown are for Installation
Type A-free inlet fan sone levels.
Speed (RPM) shown is nominal. Performance is based on actual speed of test.
Fan RPM performances may vary from actual current motor o󰀨erings for any given model. See Optisizer2 fan selection software for current motor RPM o󰀨erings
STXD & STXDe:
STANDARD 705 for Electrical
STXD:
STANDARD 762 for Grease Removal