CONSTRUCTION/SPECIFICATION CHECKLIST
Housing
Curb cap with integral deep single piece spun inlet for e󰀩cient performance and prevention of leakage into
ductwork.
Heavy-gauge aluminum housing and curb cap for strength and rigidity. Curb cap is galvanized steel on all
UL762 units.
Stainless steel exterior fasteners.
Enclosed, ventilated motor compartment isolates motor from exhaust air.
Neoprene isolators for reduction of vibration and sound.
Quick-Release latches on motor cover for easy access to motor compartment.
Water-tight conduit tube for easy electrical connection without having to wire through the breather tube.
NFPA - Model STXD is suitable for National Fire Protection Association installations. Contact factory for
required accessories.
Centrifugal Wheel
All aluminum wheel.
Backward-inclined for e󰀩ciency at higher static pressure.
Non-overloading for safe operation in ducted systems.
Curved blades for e󰀩ciency and quiet operation.
Dynamically balanced for smooth operation.
Speed Controllable Motors (STXD)
Brands are nationally recognized and locally serviced.
Standard motors are single speed, speed controllable and drip-proof.
All motors are rated for continuous duty.
Disconnect switch is standard with drip-proof motors.
Heavy-gauge steel motor brackets designed for maximum strength.
Electronically Commutated Motors (STXDe)
Brands are nationally recognized and locally serviced.
Easy speed control by DC 0-10 V variation.
Motor has motor mounted potentiometer with digital readout for easy speed adjustment.
Can be controlled by a PC or building management system.
Motor has 80% usable turndown vs. 30% on a PSC motor.
Internal motor circuitry converts 115/230 V single phase AC power to DC voltage for increased e󰀩ciencies.
All motors are rated for continuous duty.
Motor is 115/230V and 50/60 Hz.
Disconnect is standard.
Motors ship mounted as standard.
AMCA Seal
Assures accuracy of Air and Sound Performance.
cULus Label
cULus 705 Listed Power Roof Ventilator label assures electrical reliability.
MODEL STXD & STXDe