User's Manual
4- MOUNTING AND WIRING MODULE
The BL case must be installed indoor use only. It can be xed against a wall
with the screws supplied with the product.
Cabling of the transformer to the power supply:
- The BL case must be installed the nearest possible of the electric plug.
The power plug must be accessible at all me in order to unplug the device in
case of emergency.
- Make sure that the power plug on which the transformer is plugged in has
a overcurrent and short-circuit protecon breaker for 16A (20A for US).
Wiring of the 4 output lines:
- Each line must be protected by a circuit breaker which should be idened
and easily accessible.
- The 230V (120V in the U.S) cables which are used to power the 4 lines must
have either a double insulaon or a reinforced insulaon.
- Cables used for wiring must be of type H05VV-F or H03VV-F and
of secon 2x1,5mm².
Maximum electric charge :
For a 230V installaon : 4000W (16A*) total over all lines and up to only
3500W
on one single line.
For a 120V installaon : 2000W (16A*) total over all lines and up to only
1700W
on one single ligne. Use only power supply provided with product 120V 0.75A
*16A max for resisve load
1,7A max for inducve load
Max operang temperature : 45°C
P-18