Setting
Setting
n ) DRM function (applied to NZS4777.2)
The DRM function is a demand response method required by the
NZS4777.2 standard and is only applicable to NZS4777.2.
The default value is "enable". Select "Disable" to disable this function.
>Function Control
DRM Function
Enable Disable
Reactive power control, reactive power standard curve cos φ = f(P)
For VDE ARN 4105, the curve cos = f(P) should refer to curve B. The set
default value is shown in curve B.
For e8001, the curve cos = f(P) should be curve A. The set default value is
shown in curve A.
For CEI 0-21, the default value of PFLockInPoint is 1.05. When Vac> 1.05Vn,
Pac> 0.2 Pn, curve cos cp = f(P) corresponds to curve B.
0.9
0.9
Upper limit
capacitive
inductive
f (P)
Lower limit
Power Lower
Power Upper
curve A
0.3
0.7
0.2
0.8
0.50.2 1.0
0.95
0.95
cosφ
capacitive
inductive
f (P)
curve B
Reactive power control, reactive power standard curve Q= f(V)
Q
V
Qmax
-Qmax
V2sV1s
V1iV2i
V2i=0.90Vn
V2s=1.10Vn
V1s=1.08Vn=QuVlowRate
V2i=0.92Vn=QuVlowRate
0.9/0.95*
0.9/0.95*
leading
p/p
lagging
curve A
0.5 1.0
over-excited
under-excited
0.2
1
Emax
cos φ
o ) Main Breaker Limit
For power limit of smart meter or CT, the current must be set in line
with the utility's contract requirements. In case of failure to set, it
may cause a circuit breaker fault of main switchboard, adversely
aecting the charging or discharging of battery. Click Main Breaker
Limit to enter the setting interface, and then choose the
corresponding amperage according to the utility's requirements.
>Current
40 A
Main Breaker Limit
q ) Battery Heating
If the user needs the battery heating function, you can set it to turn on
here, and set the time period that needs to be heated, and the two time
periods can be set. (Only for batteries with heating function)
104
105
O ) Parallel Setting
If a parallel operation is required, the user may set it with Parallel Setting.
> Status Free
Parallel Setting
Setting
Parallel Setting
> Master
>
> Status Free
Setting
Free
>Func Select:
Enable Disable
Battery Heating
>Heating Period 1:
Start Time
00:00
Battery Heating
>Heating Period 2:
Start Time
00:00
Battery Heating
>Heating Period 1:
End Time
00:00
Battery Heating
>Heating Period 2:
End Time
00:00
Battery Heating