User Manual

Setting
Setting
ALL Test
Test report
Uvp(27.S1) test
Ft: 51.50Hz Tt:1000ms
Fs: 0.00Hz To: 998ms
F0: 0.00Hz pass
>Ofp2(81>.S2)result
Vt: 264.5V Tt: 300ms
Vs: 0.0V To: 200ms
V0: 0.0V pass
>Ovp2(59.S2)result
Vt: 92.0V Tt: 200ms
Vs: 0.0V To: 196ms
V0: 0.2V pass
>Ofp2(27.S2)result
Vt: 195.5V Tt: 400ms
Vs: 0.0V To: 200ms
V0: 0.0V pass
>Uvp2(27.S1)result
Ft: 50.50Hz Tt: 100ms
Fs: 0.00Hz To: 96ms
F0: 0.2Hz pass
>Ofp2(81>S1)result
Ft: 49.50Hz Tt: 100ms
Fs: 0.00Hz To: 98ms
F0: 0.02Hz pass
>Ufp2(81<.S1)result
Ft: 47.50Hz Tt: 400ms
Fs: 0.00Hz To: 3999ms
F0: 0.02Hz pass
>Ufp2(81<.S2)result
Vt: 253.0V Tt: 600ms
Vs: 0.0V To: 598ms
V0: 0.0V pass
>Ovp10(59.S1)result
h ) Modbus
Here you select the baud rate of the external communication protocol.
f ) Self Test (only for CEI 0-21)
The self test function allows users to test the following items. "Full test",
"Ovp(59.S2) test"27. "Uvp (s1) test", "Uvp (27. s2) test", "Ofp (81> .S1) test",
"Ufp (81 <.S1) test", "Ufp (81> .S2) test", "Ufp (81 <.S2) test",
"Ovp10 (59. s1) test".
In the self-test interface, the user can select "all tests" or a single test item
for testing.
Before testing, make sure that the inverter is connected to the grid.
All tests take about 6 minutes. And it will display "Success" and then
"Delivery".
For a single test item, it takes about a few seconds or minutes.
Click "Test Report" to view the test results of all items.
I ) External ATS
.If you want Matebox installed, you need to turn this feature on
here.”Disableis a default.
Functional Control
Disable Enable
External ATS
100
101
j ) Power Factor (applicable to specific countries, please refer to local grid
requirements)
Mode Select
Off
Power Factor
Mode Select
Over-excited
Power Factor
Select
Meter CT
CT/Meter Setting
Meter 1Addr:
1
CT/Meter Setting
Select
Enable
Disable
CT/Meter Setting
Meter 2 Addr:
2
CT/Meter Setting
Meter 1Direction:
Positive Negative
CT/Meter Setting
Meter 2 Direction:
Positive Negative
CT/Meter Setting
e ) Meter/CT Settings
The user needs to select the CT or electricity meter to connect the
inverter here. CT is a default, when users choose CT, there is only Meter 2
Addr setting. All will show on the inverter screen when users choose
Meter.
d ) Export Control
This feature allows the inverter to control the amount of electricity
output to the grid.
The factory value is the default and can be changed by the user. The
user value set by setup must be less than the maximum. If the user
does not want to supply power to the grid, set it to 0.
User value:
0W
Export Control
Func Select
Middle
Shadow Fix
Modbus
Baud Rate:
19200
Modbus
Address:
1
g ) Shadow Fix
Here, you can set the shadow tracking with four options, which are
off, low, middle, and high.