User Manual

Electrical Connection
Electrical Connection
Step 2. Plug Pocket WiFi into the DONGLE port.
74
75
Please check the Pocket WiFi user manual/Pocket LAN user manual /4G
user manual.
Ø After the inverter is checked, then conduct the following
steps
Turn on the Load switch and EPS(Off-grid) switch.
Turn on the battery switch.
Make sure the battery is well connected.
Make sure the CT are connected.
Confirm that all DC lines and AC lines are connected.
Make sure that the inverter is fixed on the wall.
Long press the “Enter “key for 5 seconds to exit the Off mode.
(The mode is factory defaulted as Off Mode)
Ensure that all ground wires are grounded.
5.8 Check All Below Steps Before Starting Inverter
Note: The RCD on the gure represents a leakage protection device
with a circuit breaker function.
N
BAT
Battery
N-BAR for loads
N-BAR for EPS(O-grid) loads
EPS(O-grid) loads
Loads
Inverter
PV 1
PV 2
E-BAR
RCD
Breaker
Grid
Breaker
Grid
EPS(O-grid)
Main Breaker/RCD
Breaker
Breaker
CT
Distribution Box
CT-R
CT-S