Wire Lengths and Voltage Rise
When planning the system, you must select the appropriate AC conductor size to minimize voltage rise. Select the
correct wire size based on the distance from the beginning of the AC branch circuit to the breaker in the load center.
Enphase recommends a voltage rise total of less than 2% for the sections from the AC branch circuit to the breaker
in the load center.
Enphase provides guidance about choosing wire size and maximum conductor lengths in the Voltage Rise Technical
Brief at enphase.com/support. Refer to this brief for voltage rise values in Enphase Q Cables and on how to
calculate voltage rise in other wire sections of the system.
Standard guidelines for voltage rise on feeder and AC branch circuit conductors might not be sufcient for
microinverter AC branch circuits that contain the maximum allowable microinverters. This is due to high inherent
voltage rise on the AC branch circuit.
Best practice: Center-feed the branch circuit to minimize voltage rise in a fully-populated branch. This
practice greatly reduces the voltage rise as compared with an end-fed branch. To center-feed a branch,
divide the circuit into two sub-branch circuits protected by a single OCPD.
Lightning and Surge Suppression
Enphase Microinverters have integral surge protection greater than most traditional inverters. However, if the
surge has sufcient energy, the protection built into the microinverter can be exceeded, and the equipment can
be damaged. For this reason, Enphase recommends that you protect your system with a lightning and/or surge
suppression device. In addition to having some level of surge suppression, it is also important to have insurance
that protects against lightning and electrical surges. Enphase has tested the devices in the following tables.
RESIDENTIAL COMMERCIAL
y Citel DS72-RS-120 surge protector; data sheet
y Delta LA-302 lightning arrestor; website
y Midnite solar surge protection device MNSPD-300 or
MNSPD-300FM (with ush mount box); website
y Citel DS73-RS-G surge protector; data sheet
y Delta LA-303 lightning arrestor; website
NOTE: Protection against lightning and resulting voltage surge
must be in accordance with local standards.