Installation manual
13
Safety, Installation, and Operations Manual
© Solaria Corporation All rights reserved. Contents subject to change without notice 8-26-19
Power Unlocked by Design
The microinverter housing is designed for outdoor installation and complies with the NEMA 250, type 6
environmental enclosure rating standard:
NEMA 6 rating denition: Indoor or outdoor use primarily to provide a degree of protection against hose-
directed water, the entry of water during occasional temporary submersion at a limited depth, and damage
from external ice formation.
The Enphase Q Cable is available with connector spacing options to accommodate installation of PV modules in
portrait or landscape orientation. For Enphase Q Cable ordering information, see “Enphase Q Cable Planning and
Ordering” on page 37.
Planning the Racking
Plan the racking position with the Microinverter in mind. Ensure that the racking does not interfere with the
microinverter and its connectors.
Grounding Considerations
The Enphase Microinverter models listed in this guide do not require grounding electrode conductors (GEC),
equipment grounding conductors (EGC), or grounded conductor (neutral). Your Authority Having Jurisdiction
(AHJ) may require you to bond the mounting bracket to the racking. If so, use UL2703 hardware or star washers.
Refer Module Installation: Step 10 for details. The microinverter itself has a Class II double-insulated rating, which
includes ground fault protection (GFP).
Branch Circuit Capacity
Plan your AC branch circuits to meet the following limits for maximum
number of microinverters per branch when protected with a 20 amp
(maximum) over current protection device (OCPD).
NOTE: * Limits may vary. Refer to local requirements to dene
the number of microinverters per branch in your area.
Utility Service Requirements
The Enphase IQ Microinverter for ACM work with single-phase service.
Measure AC line voltages at the electrical utility connection to conrm
that it is within the ranges shown:
Planning for PowerXT
®
-R-AC Module Installation
MAXIMUM* IQ 7+ MICROS
PER AC BRANCH CIRCUIT (240 VAC)
13
MAXIMUM* IQ 7+ MICROS
PER AC BRANCH CIRCUIT (208 VAC)
11
240 VOLT AC, SINGLE PHASE
L1 to L2 211 to 264 VAC
L1, L2 to ground 106 to 132 VAC
208 VOLT AC, SINGLE PHASE
L1 to L2 183 to 229 VAC
L1, L2 to ground 106 to 132 VAC