SE66.6K-SE100K Three Phase Inverter with Synergy Technology for 277-480V Grid
Three Phase Inverter with Synergy Technology
for the 277/480V Grid for North America
SE66.6KUS / SE100KUS
SE66.6KUS SE100KUS
OUTPUT
Rated AC Power Output
66600
100000
VA
Maximum AC Power Output
66600
100000
VA
AC Output Line Connections
4-wire WYE (L1-L2-L3-N) plus PE
AC Output Voltage Minimum-Nominal-Maximum
(1)
(L-N)
244 - 277 - 305
Vac
AC Output Voltage Minimum-Nominal-Maximum
(1)
(L-L)
422.5 - 480 - 529
Vac
AC Frequency Min-Nom-Max
(1)
59.3 - 60 - 60.5
Hz
Maximum Continuous Output Current (per Phase) @277V
80
120
A
GFDI Threshold
1
A
Utility Monitoring, Islanding Protection, Configurable Power
Factor, Country Configurable Thresholds
Yes
INPUT
Maximum DC Power (Module STC) / Unit
100000 / 50000
150000 / 50000
W
Transformer-less, Ungrounded
Yes
Maximum Input Voltage DC to Gnd
500
Vdc
Maximum Input Voltage DC+ to DC-
1000
Vdc
Nominal Input Voltage DC to Gnd
425
Vdc
Nominal Input Voltage DC+ to DC-
850
Vdc
Maximum Input Current
2 x 40
3 x 40
Adc
Maximum Input Short Circuit Current
120
Adc
Reverse-Polarity Protection
Yes
Ground-Fault Isolation Detection
350kΩ Sensitivity per Unit
CEC Weighted Efficiency
98.5
%
Nighttime Power Consumption
< 12
W
ADDITIONAL FEATURES
Supported Communication Interfaces
RS485, Ethernet, Cellular GSM (optional)
Rapid Shutdown
NEC2014, NEC2017 and NEC2020 compliant/certified, upon AC Grid Disconnect
RS485 Surge Protection
Built-in
DC SAFETY SWITCH
DC Disconnect
1000V / 2 x 40A
1000V / 3 x 40A
STANDARD COMPLIANCE
Safety
UL1741, UL1741 SA, UL1699B, UL1998, CSA 2.22
Grid Connection Standards
IEEE 1547, Rule 21, Rule 14 (HI)
Emissions
FCC part15 class A
INSTALLATION SPECIFICATIONS
Number of units
2
3
AC Output Conduit Size / Max AWG / Max PE AWG
1.5” / 2/0 / 6
2” / 4/0 / 4
DC Output Conduit Size / Terminal Block AWG Range /
Number of Strings
(2)
2 x 1.25” / 6-14 / 6 strings 2 x 1.25” / 6-14 / 9
strings
Dimensions (H x W x D)
Primary Unit: 37 x 12.5 x 10.5 / 940 x 315 x 260;
Secondary Unit: 21 x 12.5 x 10.5 / 540 x 315 x 260
in / mm
Weight
Primary Unit: 105.8 / 48; Secondary Unit 99.2 / 45
lb / kg
Operating Temperature Range
-40 to +140 / -40 to +60
(3)
F / ˚C
Cooling
Fan (user replaceable)
Noise
< 60
dBA
Protection Rating
NEMA 3R
Mounting
Brackets provided
(1) For other regional settings please contact SolarEdge support
(2) Single input option per unit (up to 3AWG) available
(3) De-rating from 50
C
© SolarEdge Technologies, Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All
other trademarks mentioned herein are trademarks of their respective owners. Date: 02/2021 DS-00005-1.0-NA. Subject to change without notice.