SE43.2K - Three Phase Inverter with Synergy Technology for the 208V Grid

SE43.2KUS
OUTPUT
Rated AC Power Output 43200 VA
Maximum AC Power Output 43200 VA
AC Output Line Connections 4-wire WYE (L1-L2-L3-N) plus PE or 3 wire Delta
AC Output Voltage Minimum-Nominal-Maximum
(1)
(L-N) 105-120-132.5 Vac
AC Output Voltage Minimum-Nominal-Maximum
(1)
(L-L) 183-208-229 Vac
AC Frequency Min-Nom-Max
(1)
59.3 - 60 - 60.5 Hz
Maximum Continuous Output Current (per Phase) @208V 120 A
GFDI Threshold 1 A
Utility Monitoring, Islanding Protection, Congurable Power Factor,
Country Congurable Thresholds
Ye s
INPUT
Maximum DC Power (Module STC), Inverter / Unit
64800 / 21600
W
Transformer-less, Ungrounded Ye s
Maximum Input Voltage DC to Gnd 300 Vdc
Maximum Input Voltage DC+ to DC- 600 Vdc
Nominal Input Voltage DC to Gnd 200 Vdc
Nominal Input Voltage DC+ to DC- 400 Vdc
Maximum Input Current 38 x 3 Adc
Maximum Input Short Circuit Current 135 Adc
Reverse-Polarity Protection Ye s
Ground-Fault Isolation Detection 350kΩ Sensitivity per Unit
CEC Weighted Eciency 97 %
Nighttime Power Consumption < 12 W
ADDITIONAL FEATURES
Supported Communication Interfaces RS485, Ethernet, Cellular GSM (optional)
Rapid Shutdown NEC2014, NEC2017 and NEC2020 compliant/certied, upon AC Grid Disconnect
RS485 Surge Protection Built-in
DC SAFETY SWITCH
DC Disconnect 1000V / 3 x 40A
STANDARD COMPLIANCE
Safety UL1741, UL1741 SA, UL1699B, UL1998, CSA 2.22
Grid Connection Standards IEEE 1547, Rule 21, Rule 14 (HI)
Emissions FCC part15 class A
INSTALLATION SPECIFICATIONS
Number of units 3
AC Output Conduit Size / Max AWG / Max PE AWG 2” / 4/0 / 4
DC Output Conduit Size / Terminal Block AWG Range /
Number of Strings
(2)
2 x 1.25” / 6-14 / 9 󰎯rings
Dimensions (H x W x D)
Primary Unit: 37 x 12.5 x 10.5 / 940 x 315 x 260;
Secondary Unit: 21 x 12.5 x 10.5 / 540 x 315 x 260
in / mm
Weight Primary Unit: 105.8 / 48; Secondary Unit 99.2 / 45 lb / kg
Operating Temperature Range -40 to +140 / -40 to +60
(3)
F / ˚C
Cooling Fan (user replaceable)
Noise < 60 dBA
Protection Rating NEMA 3R
Mounting Brackets provided
(1) For other regional settings please contact SolarEdge support
(2) Single input option per unit (up to 3AWG) available
(3) For power de-rating information refer to: https://www.solaredge.com/sites/default/les/se-temperature-derating-note-na.pdf
Three Phase Inverter with Synergy Technology
for the 208V Grid for North America
SE43.2KUS
© SolarEdge Technologies, Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc.
All other trademarks mentioned herein are trademarks of their respective owners. Date: 03/2021 DS-000030-1.0-NA. Subject to change without notice.