Installation Guide
4.
Insert the cable through the ACdrill guide that was opened.
NOTE
Connect the equipment grounding before connecting the AC wires to the
AC terminal block.
Veillez à relier le conducteur de PE (la terre) avant de connecter les fils CA
au bornier CA.
5. Connect the grounding wire to the grounding terminal block and tighten with a
torque of
15N*m / 12 lb*ft.
6.
Remove the screws from the AC terminal blocks.
NOTE
Apply heat shrink insulation to the lug barrels.
7.
Crimp the lugs on the AC wires.
CAUTION!
Only use compression lugs of the one -hole standard barrel 600v type . Do
not use mechanical lugs (chair lugs) as they may pose a safety risk.
Three Phase Inverter with Synergy Technology Installation MAN-01-00401-1.5
46 Connecting the AC Grid and Grounding to the Connection Unit